Faber Respect Premium OC Installation Manual Download Page 10

 

Installation manual Respect Premium OC

 

 

10 < 

<

 

<

 

3

 

Installation requirements 

3.1

 

Appliance 

 

This appliance may not be installed in a 
chlorine-containing environment. (Pools 
etc.). 

 

This appliance must be build into an 
existing or new false chimney. 

 

For appliances with flexible gas pipes, the 
control unit (fig. 1.2) is placed on the right 
side of the crate for transport reasons. 
Detach and mount it together with the 
remote access door in as low as possible 
position in the false chimney. 
(To prevent damage to cables and pipes 
during transport, they are bound together 
by tie wraps. Remove these to ensure 
proper operation of the appliance.) 

3.2

 

False chimney 

 

The false chimney should be of non-
combustible material. 

 

The space above the fire should always be 
ventilated using grids with minimal free 
passage of 200cm² per grid.  

 

The false chimney construction should not 
rest on the build-in frame of the fireplace. 

3.3

 

Discharge and outlet requirements 

First, carry out a flue calculation (see chapter 11) 
and place the right flue restrictor before installing 
the outlet! (Generally a 30mm flue restrictor is 
installed). 

 

For supply and discharge always use the 
prescribed and to be supplied Faber flue 
materials. Please contact Glen Dimplex 
Benelux B.V.. Only with use of these 
materials Faber can guarantee proper 
performance. 

 

The distance to combustible materials 
must be min. 50mm, calculated from 
outside of the flue material (EN 1856-1 
T600 N1 D Vm – L20040 O(50)). 

 
Outlets (fig. 1.1) 
The balanced flue pipe for combined air supply and 
discharge can use a wall terminal or a roof 
terminal. Verify that the desired outlet meets the 
local regulations regarding pollution and 
ventilation openings. 
 

 

Please note! 
For proper functioning, the outlet must at 
least be 0,5m away from: 

 

Corners of the building; 

 

Roof overhangs and balconies; 

 

Roof edges (with the exception of the 
ridge edge, see chapter 15). 
 

C11, outlet via facade 
Through a wall or façade, use a Faber wall outlet. 
Depending on the flue calculation this can be 
100/150mm or 130/200mm. 
 
C31, outlet via roof 
For a (flat) roof, use a Faber roof outlet with a 
diameter of 100/150mm. 
 
C91, existing chimney 
For an existing chimney, use a Faber chimney 
outlet with a diameter of 100/150mm. 
In this case the existing chimney acts as air inlet an 
inserted flexible stainless steel pipe discharges the 
flue gas. The top (Faber chimney cover plate) and 
the bottom (Faber chimney connection set) should 
be airtight. 
Depending on the calculated flue diameter, you 
must use a flexible stainless steel pipe of 
Ø100mm (article number AJ005503) or Ø130mm 
(article number AJ005603) as specified by Faber. 
For this, contact Glen Dimplex Benelux B.V. 
 

 

Please note! 

 

The minimum chimney diameter for a 
130mm flexible stainless steel pipe must 
be 200x200mm and for a 100mm flexible 
stainless steel pipe and 150x150mm. 

 

Don’t connect more than one fire at the 
existing chimney. 

 

The chimney must be in good condition: 

o

 

No leakage; 

o

 

Well cleaned. 

 

For more information about the connections to 
existing chimney ducts, please request the 
installation instructions “Chimney Connection Set”. 

4

 

Preparation and installation 
instructions 

4.1

 

Gas connection 

The gas connection must comply with the 
applicable local standards.  
 

 

Please note! 

 

Provide a flexible gas connection with at 
least 0,5m extra length, so that the 
control unit can be removed for 
installation and service! 

 

Calculate the gas pipe so that no 
pressure drop occurs. 

 

 

Summary of Contents for Respect Premium OC

Page 1: ...Installation manual Respect Premium OC ENG 40011335 2009 ...

Page 2: ...Installation manual Respect Premium OC 2 ...

Page 3: ...Installation manual Respect Premium OC 3 ...

Page 4: ...Installation manual Respect Premium OC 4 1 0 1 1 1 2 1 3 1 4 1 5 1 6 A A ...

Page 5: ...Installation manual Respect Premium OC 5 1 7 1 8 1 9 2 0 Y X B C D ...

Page 6: ...Installation manual Respect Premium OC 6 2 1 3 1 3 2 3 3 3 4 ...

Page 7: ...Installation manual Respect Premium OC 7 3 5 3 6a 3 6b 3 6c 3 6d 4 0 A B B A ...

Page 8: ...Installation manual Respect Premium OC 8 ...

Page 9: ...e It is advisable to always install a screen for the fireplace if children elderly or disabled people are present in the same room as the fireplace If regularly vulnerable persons can be present in the room without supervision sufficient protection must always be placed around the fireplace This appliance must be installed according with the rules in force and used only in a sufficiently space The...

Page 10: ...ts the local regulations regarding pollution and ventilation openings Please note For proper functioning the outlet must at least be 0 5m away from Corners of the building Roof overhangs and balconies Roof edges with the exception of the ridge edge see chapter 15 C11 outlet via facade Through a wall or façade use a Faber wall outlet Depending on the flue calculation this can be 100 150mm or 130 20...

Page 11: ...ight of 780mm With the upper part removed the appliance can be transported on its back fig 1 4 Please note The transport plate may only be removed after the fireplace has been fixed to the wall see fig 1 8 4 6 Positioning the fireplace Take into account the installation requirements see chapter 3 Place the fireplace at the right place and level it see fig 1 9 D Rough height adjustment With the adj...

Page 12: ...optional supplied Faber ventilation grids article number A9296400 or a similar alternative with a minimum free passage of 200cm per grid in the space above the fire when building the false chimney Within the false chimney an horizontal screen plate made of non combustible material must be installed just above the ventilation openings see fig 1 0 A 5 Installing glass Please note Before installing t...

Page 13: ...ame distribution is good Move or remove any ash material to create a nice glow bed Install the front glasses and check the fire image 6 2 Pebbles Grey stones See the supplied decoration instruction card or chapter 18 2 or 18 3 Divide the pebbles grey stones over the entire bottom Avoid a double layer Please note Keep the pilot flame and 2nd thermocouple free from pebbles grey stones Start the fire...

Page 14: ...must not be greater than 1 100 Example CO2 is 4 and CO is 400ppm measured at the highest point If the ratio is greater than 1 100 or flue gases are measured in the air supply check the points in section 7 1 8 Instructions for client Recommend that the fire should be checked annually by a qualified specialist to ensure the safe use and to guarantee a long service life Provide instructions on the op...

Page 15: ...on in the drawings fig 12 1 12 2 and 12 3 Total Horizontal Length THL THL is the Total Horizontal Length and consists of elbows and pipes entirely in the horizontal plane See elbows I K and Q and the elements H J L M P and R fig 12 1 and 12 2 Horizontal length The Horizontal Length consists of the elements H J L M P and R fig 12 1 and 12 2 Elbows 90 in the horizontal plane Horizontal elbows are el...

Page 16: ...0 x x x x x x x x x x 9 60 20 x x x x x x x x x x 10 60 20 x x x x x x x x x x 11 70 20 x x x x x x x x x x 12 70 20 x x x x x x x x x x 13 70 20 x x x x x x x x x x 14 70 20 x x x x x x x x x x 15 80 20 x x x x x x x x x x 16 80 20 x x x x x x x x x x 17 80 20 x x x x x x x x x x 18 80 20 x x x x x x x x x x 19 80 20 x x x x x x x x x x 20 80 20 x x x x x x x x x x 21 80 20 x x x x x x x x x x 22...

Page 17: ... 40 80 40 80 40 80 40 70 40 70 40 70 40 65 40 x x 12 80 40 80 40 80 40 80 40 80 40 70 40 70 40 70 40 65 40 x x 13 85 40 80 40 80 40 80 40 80 40 70 40 70 40 70 40 65 40 x x 14 85 40 85 40 80 40 80 40 80 40 70 40 70 40 70 40 65 40 x x 15 85 40 85 40 80 40 80 40 80 40 70 40 70 40 70 40 65 40 x x 16 85 40 85 40 80 40 80 40 80 40 70 40 70 40 70 40 65 40 x x 17 85 40 85 40 80 40 80 40 80 40 70 40 70 40 ...

Page 18: ...Installation manual Respect Premium OC 18 12 Examples flue materials ...

Page 19: ... 5 Flue length 2m or more 2 Bend 90 0 1 Bend 45 30 or 15 0 2 Roof terminal 1 Wall terminal 0 Total Vertical Height TVH measured height rounded value meter meter Total Horizontal Length THL Calculation Part number x value result rounded value Total Length in meters x 1 90 Bend vertical to horizontal x 0 4 45 Bend vertical to horizontal x 0 2 90 Bend in horizontal direction x 1 5 45 Bend in horizont...

Page 20: ... installation is not possible Solution Change the TVH or THL Results Restrictor size Value for the comma mm Extra information Value behind the comma mark Install the air restrictor plate see installation manual 0 1 Install adapter 100 150 direct on top of the fire 0 2 In case of wall terminal install adapter 100 150 before the last bend in case of roof terminal just before the terminal 0 3 In case...

Page 21: ...D D Energy efficiency index EEI 73 73 73 Type heating output control room temperature no no no no no yes Glen Dimplex Benelux Saturnus 8 Heerenveen The Netherlands With mechanical control of the room temperature by thermostat Control of room temperature with open window detection no With electronic control of the room temperature With electronic control of the room temperature plus day time switch...

Page 22: ...sition outlet Distance mm D Under a gutter 500 E Under a roof edge 500 F Under a carport or balcony 500 G Vertical downpipe 300 H Inside and outside corners 500 J From wall surface to a wall outlet 1000 K Two gable outlets against over each other 1000 L Distance between two roof outlets 450 M Two roof outlets above each other on a pitched roof 1000 N Two gable outlets next to each other 1000 Short...

Page 23: ...Installation manual Respect Premium OC 23 16 Troubleshooting guide ...

Page 24: ...Installation manual Respect Premium OC 24 ...

Page 25: ...Installation manual Respect Premium OC 25 17 Dimensional drawings 17 1 Respect Premium OC ...

Page 26: ...Installation manual Respect Premium OC 26 17 2 Remote access door article number A9299463 ...

Page 27: ...Installation manual Respect Premium OC 27 17 3 Ventilation grid article number A9296400 ...

Page 28: ...Installation manual Respect Premium OC 28 18 Decoration instruction card 18 1 Log set ...

Page 29: ...Installation manual Respect Premium OC 29 ...

Page 30: ...Installation manual Respect Premium OC 30 18 2 Pebbles 18 3 Grey stones ...

Page 31: ...Installation manual Respect Premium OC 31 ...

Page 32: ...www faberfires com contact faberfires com Saturnus 8 NL 8448 CC Heerenveen Postbus 219 NL 8440 AE Heerenveen ...

Reviews: