 Calculation of flue system 

 

Using the flue calculation spread sheet, you 

can make a flue calculation. (see chapter.13) 
There is also a App. available, Which can be 

downloaded with the following code.   

 

The possibilities for the lengths of flue pipes 

and the possible restrictors have been 
recorded in a  table (see chapter 11.11 and 

11.12)  This table works with a Starter length 
(STL) Total vertical height (TVH) and Total 

horizontal length (THL) 

11.1

 

Starter length  (STL) 

Is the first flue part installed on the fireplace 
and represents a certain value (fig.12.2 and12 

3 A,N, F) 
This value is showed in the top row of the 

table ( see table 11.11 and 11.12)  

11.2

 

Total Vertical Height  (TVH)  

TVH is the total height, measured from the 
top of the fireplace to the 

terminal. Indicated as TVH., This can be 
measured or determined from the 

construction drawing.  
see also the TVH indication in the drawings. 
(fig. 12.1 12.2 and 12 3: TVH)  

11.3

 

Total Horizontal length:(THL) 

THL is the calculated Horizontal Length and 

may consist of bends or pipe lengths  
in the horizontal direction. Indicated as I, K, 

and Q for bends and H, j, L, M, P  
and R for pipes.

 (

fig.12.1 and 12.2) 

11.4

 

Total length of horizontal flue: 

In the drawings the horizontal pipe lengths 
consists of the elements H, J, L,  

M, P and R. 

(fig. 12.1 and 12.2 ) 

 

  

11.5

 

 90° bends in the horizontal direction 

Only bends in the horizontal direction. 

Indicated as I, K and Q.  (fig.12.1,12.2 and 
12.3) 

11.6

 

45°of 30 bends in the horizontal 
direction  

Only bends in the horizontal direction. 

11.7

 

90°bends from vertical to horizontal 
direction  

90° bends from vertical to horizontal 
direction or reversed. Indicated as G, O and 

S. fig.12.2 and 12.3 ) 

11.8

 

45° of 30 °bends from vertical to 

horizontal direction  

30° or 45° bends in the vertical direction. 

Indicated as B and D. (fig 12.1 )  

11.9

 

Flue pipes under 45° or 30° 

gradient:: 

Flue pipes installed with an angle of 30° or 

45° in the vertical direction. 
Indicated as C. (fig 12.1 )  Only possible in 

combination with 2 pieces of 45° or 30°  
bends in the vertical plane 

 

11.10

 

Table: 

NOTE :  for this appliance is a table 
for the flue pipe diameter  100/150mm 

(11.11) and a table for the flue 
diameter 130/200mm (11.12) 

  

Find the correct vertical (TVH) and horizontal 
(THL).lengths in the table. 

In case of an “x”, or if the values are outside 
the table, the combination is not permitted.in 

this case, change the length of the TVH or 
THL. If a value is specified, verify that the 

calculated STL value is not lower than 
indicated in the table. If so than the STL must 
be changed 

The value found indicates the width of the 
restrictor to be placed  ("0"  means no 

restrictor should be placed). 
Generally a 30mm restrictor is pre-installed. 

(See fig. 2.6  B  ) 
 

 

 

 

 

 

Summary of Contents for Respect OC

Page 1: ...Respect OC 40011335 1235 Installation manual ENG ENG ...

Page 2: ...1 L 1 1 1 2 1 3 1 4 2 1 2 2 2 3 A A A ...

Page 3: ...2 L 2 4 2 5 2 6 A B A C B ...

Page 4: ...3 L 3 1 3 2 3 3 3 4 3 5 3 6 ...

Page 5: ...4 L 3 7 A B ...

Page 6: ...5 L 4 1 4 2 4 3 A A A A A A ...

Page 7: ...the fire run on maximum setting for several hours so that the lacquer coating will have an opportunity to set and possible vapours released can be safely removed by ventilation We advise you to be outside the room as much as possible during this process Please note that all transport packaging should be removed children or pets should not be present in the room 3 Installation requirements 3 1 The ...

Page 8: ...ame if necessary and the glass and take the separately wrapped parts out of the appliance Prepare the gas connection to the gas control valve 4 4 Moving the appliance If necessary the upper parts of the appliance can be taken of this gives a minimum dimension of the appliance 780mm then the appliance can be transported on the back side see fig 2 1 It is only allowed to remove the transport plate a...

Page 9: ...build in frame The chimney construction may not resting on the build in frame 5 Placing the decorative material It is not allowed to add different or more materials to the combustion chamber Always keep the pilot burner and the second thermocouple free from decorative material See fig 4 1 A up to 4 3 A Do not toss all the decorative material onto the burner all at once it can be obstructed by dust...

Page 10: ...is on at full gas mark and when it is on the pilot light If the inlet pressure is too high you are not permitted to connect the appliance Measuring the burner pressure Only perform this measurement if the inlet pressure is correct Open the pressure gauge nipple A see fig 1 4 a few turns and connect a pressure gauge hose to the gas control valve The pressure must correspond with the value indicated...

Page 11: ...ters 9 Annual maintenance 9 1 Service and cleaning Check and clean if necessary after checking o The pilot light o The burner o The combustion chamber o The glass o The logs for possible fractures o The outlet 9 2 Replace o If necessary the chips embers o in an LPG flat burner replace the burner sheet 9 3 Cleaning the glass Most of the deposits can be removed with a dry cloth You can use ceramic h...

Page 12: ...s of the elements H J L M P and R fig 12 1 and 12 2 11 5 90 bends in the horizontal direction Only bends in the horizontal direction Indicated as I K and Q fig 12 1 12 2 and 12 3 11 6 45 of 30 bends in the horizontal direction Only bends in the horizontal direction 11 7 90 bends from vertical to horizontal direction 90 bends from vertical to horizontal direction or reversed Indicated as G O and S ...

Page 13: ...x x x x x 13 70 2 x x x x x x x x 14 70 2 x x x x x x x x 15 80 2 x x x x x x x x 16 80 2 x x x x x x x x 17 80 2 x x x x x x x x 18 80 2 x x x x x x x x 19 80 2 x x x x x x x x 20 80 2 x x x x x x x x 21 80 2 x x x x x x x x 22 80 2 x x x x x x x x 23 80 2 x x x x x x x x 24 80 2 x x x x x x x x 25 80 2 x x x x x x x x 26 80 2 x x x x x x x x 27 80 2 x x x x x x x x 28 80 2 x x x x x x x x 29 80 ...

Page 14: ...65 4 13 85 4 80 4 80 4 80 4 80 4 70 4 70 4 70 4 65 4 14 85 4 85 4 80 4 80 4 80 4 70 4 70 4 70 4 65 4 15 85 4 85 4 80 4 80 4 80 4 70 4 70 4 70 4 65 4 16 85 4 85 4 80 4 80 4 80 4 70 4 70 4 70 4 65 4 17 85 4 85 4 80 4 80 4 80 4 70 4 70 4 70 4 65 4 18 85 4 85 4 80 4 80 4 80 4 70 4 70 4 70 4 65 4 19 85 4 85 4 80 4 80 4 80 4 70 4 70 4 70 4 65 4 20 85 4 85 4 80 4 80 4 80 4 70 4 70 4 70 4 65 4 21 85 4 85 ...

Page 15: ...14 L 12 Example fig 12 1 fig 12 2 fig 12 3 ...

Page 16: ...om 2M or more 2 Bends 90 0 1 Bends 45 30 of 15 0 2 Roof terminal 1 Wall terminal 0 Total Vertical Height TVH measured height rounded value meter meter Total Horizontal Length THL calculate Part number x value result rounded value Total length in meters x 1 90 bends vertical to horizontal x 0 4 45 bends vertical to horizontal x 0 2 90 bends in the horizontal direction x 1 5 45 bends horizontal dire...

Page 17: ...olution Start length to low see for the minimum length in the top row of the table Results Restrictor size Found value for the comma mm Extra information Found value behind the comma Mark which is applied Install the Air restrictor plate see installation manual 0 1 Install adapter 100 150 direct on top the fire 0 2 In case of wall terminal install adapter 100 150 before the last bend in case of ro...

Page 18: ...bar gr h 1140 970 Burner pressure at full mark mbar 10 23 0 28 Injector main burner mm 7x0 89 7x1 09 7x0 54 7x0 61 7x0 54 7x0 61 Reduced input restraint mb Adjustable 4 4 Adjustable 14 3 Adjustable 17 Pilot assembly SIT 145 SIT 145 SIT 145 Code 36 23 23 Diameter inlet outlet mm 200 130 200 130 200 130 Gas control valve GV60 GV60 GV60 Gas connection 3 8 3 8 3 8 Electrical connection V 220 220 220 B...

Page 19: ...18 L 15 Dimensions ...

Page 20: ...19 L ...

Page 21: ...20 L ...

Page 22: ...21 L ...

Page 23: ...22 L ...

Page 24: ...www faber nl info faber nl Saturnus 8 NL 8448 CC Heerenveen Postbus 219 NL 8440 AE Heerenveen T 31 0 513 656500 F 31 0 513 656501 Dealer info ...

Reviews: