74
No spark at pilot burner.
Check spark gap; Check for spark in location along cable.
Check spark on the receiver by disconnecting the spark
cable from the receiver.
Inappropriate inlet pressure
Air seal issue around pilot.
Inspect and correct as needed.
Clogged pilot gas line.
stem-lighter.
Reset receiver and attempt to re-ignite.
Valve is defective
Replace valve
Receiver is defective
Replace receiver and reprogram code.
Pilot is lit, and control continues to spark. Valve shuts after 10-30 seconds.
Over tightened thermocouple interrupter
Contact customer service or gas technician
Thermocouple is defective
Replace thermocouple
Receiver is defective
Replace receiver
Pilot is lit and sparking stops. Valve shuts after 3-60 seconds. Valve does not operate manually.
Not enough voltage generated from the thermocouple
or too much resistance in the circuit.
Use a digital multimeter set in the mV range and measure
the voltage by connecting the test leads to the spade
connector. Spade connector is located on the outer
voltage must be at least 5 mV. The manufacturer must
specify the drop time for the application. The drop time can
be measured after the thermocouple is heated.
Low inlet pressure.
necessary.
Thermocouple is defective
Replace thermocouple
Valve is defective
Replace valve
3 short beeps while the motor turns
Receiver batteries are low
Low inlet pressure
Contact customer service or gas technician
handset.
Main gas burner line is crimped
Contact customer service or gas technician
Contact customer service or gas technician
Valve is defective
Replace valve
Summary of Contents for Matrix FMG3326F
Page 1: ......
Page 9: ...9 FaberFires com Maintenance Log Service Date Notes...
Page 19: ...19 FaberFires com Remote Control Instructions...
Page 20: ...20...
Page 21: ...21 FaberFires com...
Page 22: ...22...
Page 23: ...23 FaberFires com...
Page 38: ...38...
Page 70: ...70 Operation Inspection...
Page 78: ......