Installation manual MatriX 800-1050x500 RD,ST H
23 <
<
<
<
15
Outlet position
Please note!
These rules apply only for the proper functioning of the unit, for ventilation and environmental
protection you need to comply with the applicable rules as defined in the building regulations.
Location
Position outlet
Distance mm
D
Under a gutter
500
E
Under a roof edge
500
F
Under a carport or balcony
500
G
Vertical downpipe
300
H
Inside and outside corners
500
J
From wall surface to a wall outlet
1000
K
Two gable outlets against over each other
1000
L
Distance between two roof outlets
450
M
Two roof outlets above each other on a pitched roof
1000
N
Two gable outlets next to each other
1000
Short roof terminal.
Only for existing
Chimney connection.
Extension pipe over roof.
Summary of Contents for MatriX 800/500 RD H
Page 2: ...Installation manual MatriX 800 1050x500 RD ST H 1...
Page 3: ...Installation manual MatriX 800 1050x500 RD ST H 2...
Page 4: ...Installation manual MatriX 800 1050x500 RD ST H 3 1 0 1 1 1 2 1 3 1 4...
Page 6: ...Installation manual MatriX 800 1050x500 RD ST H 5 2 1a 2 1b 3 0a 3 0b 3 1a 3 1b 4 0 4 1...
Page 7: ...Installation manual MatriX 800 1050x500 RD ST H 6 4 2 4 3 4 4 4 5 4 6 4 7 4 8 4 9...
Page 8: ...Installation manual MatriX 800 1050x500 RD ST H 7 5 0 6 0 6 1...
Page 19: ...Installation manual MatriX 800 1050x500 RD ST H 18 12 Examples flue materials...
Page 23: ...Installation manual MatriX 800 1050x500 RD ST H 22 14 2 MatriX 1050 500 RD H ST H...
Page 30: ...Installation manual MatriX 800 1050x500 RD ST H 29 18 3 Control box FAB1806...
Page 33: ...Installation manual MatriX 800 1050x500 RD ST H 32...
Page 34: ...Installation manual MatriX 800 1050x500 RD ST H 33...
Page 35: ...Installation manual MatriX 800 1050x500 RD ST H 34...