37
FaberFires.com
Vent Termination
2-7 elbow zone
2-6 elbow zone
2-5 elbow zone
2-4 elbow zone
2-3 elbow zone
2 elbow zone
0 elbow
zone
V+H ≤ 40 ft.
H ≤ 20 ft.
V + H are measured from
the centre of the vent elbows.
Elbows are considered as 90°.
Two 45° elbows = One 90° elbow.
ALL APPLIANCES
(NATURAL GAS ONLY)
10'
15'
20'
5'
5'
6'
10'
15'
20'
25'
30'
35'
40'
0°
0°
Base of
air collar
Note:
A 6' (1 .83 m) minimum
vertical rise is considered the
minimum practical dimension for
the specific appliance enclosure
and a minimal building structure .
However, a greater minimum
vertical rise may be needed
to suit the specific application
constraints or local codes and /
or regulatory requirements .
Allowable Vent Configurations for Vertical Vent Terminations
(For All Models)
V
ertical Ris
e (V)
Horizontal Run (H)