7 <
<
<
<
L
L
3
Installation requirements
Note: Since the appliance is a source of heat, circulation of air occurs. Therefore it is of
importance that you do not use the appliance shortly after a renovation of the home.
Because of the natural circulation of air, moist and volatile components from paint,
building materials, carpet etc. will be attracted. These components can settle onto cold
surfaces in the form of soot.
As on all heat producing appliances, soft furnishings such as blown vinyl wallpaper placed
too near to the appliance may become scorched or discoloured. This should be born in
mind when installing the appliance.
3.1
Builders opening
The appliance can be installed in a new made hollow wall construction only. For the
dimensions of the appliance, see appendix F.
In both cases keep the following in mind:
•
do not place the appliance on combustible materials or carpets
•
both walls have to be made of non-combustible material (e.g. Promatect)
•
do not place the lintel, surround or marble stone directly onto the appliance. If
possible, apply a lintel made of cement or something similar
•
always ventilate the space above the appliance. Use a Faber ventilation grid
•
to avoid cracking, the plaster has to dry for at least 1 day per millimetre plaster
•
to avoid discolouring the plaster has to be heat resistant to min. 100 °C
3.2
Flue requirements
•
The appliance is of the type C11/C31. The appliance will need to be supplied with
the approved flue pipes and terminal, it is not possible to supply your own
•
a horizontal extension with elbows is allowed for a maximum of 6 meters
(depending on the situation)
•
Vertical flue routing between 0.5 – 12 meter (depending on situation)
Determine on the base of the example calculations in Appendix A and on the base of the
table in Appendix B if the desired situation is possible. To establish this you will need to
calculate:
•
The effective height (this is the real difference in height between the upper side of
the appliance and the terminal)
•
The total horizontal extension. This is the total horizontal flue length where:
1.
each elbow, which is in the horizontal area, counts for 2 meters
2.
each 90-degree bend, which is in the horizontal area, counts for 2 meter
3.
each 45-degree bend, which is in the horizontal area, counts for 1 meter
Summary of Contents for Honest
Page 1: ...Honest Installationguide Sity Gas 40010739 0902 ...
Page 3: ... 2 Placing the log set 2 1 2 2 2 3 2 4 ...
Page 4: ...3 L L Placing the glass 3 1 3 2 3 3 3 4 3 5 3 6 ...
Page 19: ... 18 Appendix F Dimensions ...
Page 20: ...19 L L Appendix G Ventilation Grid ...
Page 21: ... 20 Appendix H Service Hatch ...
Page 22: ......
Page 23: ... 2 ...