background image

INSTALLATION

This equipment must be installed in accordance with all local and national 
codes and regulations. 

PIPE INSTALLATION

The pipe layout is designed using the PipeIQ software package. Refer to the 
Comprehensive Instruction Manual to design the pipe network. All pipe must 
be installed in accordance with local and national codes and regulations. The 
pipe network should be complete before proceeding with the physical and 
electrical system installation.

PHYSICAL UNIT INSTALLATION

WARNING

Make sure that there are no pipes or electrical wires within the wall before 
drilling any mounting holes

SECURING THE MOUNTING BRACKET

The typical mounting location for the FAAST XS unit is on the wall. The unit 
is mounted to the wall using the enclosed mounting plate. Figure 1 shows the 
wall mounting plate. For easier access to the FAAST XS unit, it is preferred to 
position the mounting plate in an easily accessible location.

 

1.   Place the mounting bracket on the wall in the desired location and 

use it as a template to locate the necessary mounting holes.

 

2.   Mark the hole locations and remove the bracket. It is recommended 

to secure the bracket using both mounting holes. 

 

3.   Using a drill and the proper size bit for your mounting hardware, drill 

the necessary holes.

 

4.   Use appropriate fasteners to accommodate the mounting surface and 

FAAST XS device weight. 

 

5.  Secure the bracket to the wall.

FIGURE 1: WALL MOUNTING PLATE

5.800

2.500

3.500

.300

.300, 1/4 in.,

20 TPI Mounting Stud

3.860

ASP127-00

MOUNTING THE DETECTOR TO THE BRACKET

Once the mounting bracket has been attached, the unit is ready to secure onto 
the bracket. Perform the following procedure to mount the unit.

 

1.   Before installing the unit onto the bracket, remove the appropriate con-

duit caps from the top or left side of the unit to match the orientation of 
the wiring. Locate the conduit openings around the wiring access door.

 

2.   Align the unit with the three mounting clips and the mounting stud 

on the left side. 

 

3.   Push the unit down onto the mounting clips and secure it with the 

supplied washer and nut on the mounting stud protruding through 
the mounting slot shown in Figure 1. 

FIGURE 2: MOUNTING SLOTS FOR MOUNTING STUDS

10.310

9.000

4.680

2.500

6.415

ASP126-00

CONNECTING THE AIR SAMPLING PIPE

ATTENTION

Detailed pipe network information and best practices can be found in the Pipe 
Installation Guide, available for download at systemsensor.com/faast

The input and output ports are designed to accept nominal one inch pipe 
(25mm). The input and output ports are tapered to provide fast, easy, push-fit 
connection of the sampling pipe to the unit. Perform the following procedure 
to connect the air sampling pipe to the unit.
 

1.   Square off and de-burr the end of the sampling pipe. Ensure that the 

pipe is free from any particles that might interfere with the pipe con-
nection. 

 

2.   Remove the input plug from the input port being used (either the top 

or bottom of the unit). 

 

3.   Inset the air sampling pipe into the port, ensuring a snug fit. DO NOT 

glue this pipe.

EXHAUST PIPE

The device must always be exhausted in to the space that it is monitoring. 
There are some circumstances where it may be necessary to connect a pipe 
to the exhaust port to divert the exhaust away from the location of the unit. 
Adding as little as 2ft of exhaust pipe also acts as a muffler for the fan – ensur-
ing quieter operation. Perform the following procedure to connect the exhaust 
pipe to the unit.

 

3 ASUG80001

Summary of Contents for XS 7100X

Page 1: ...Length 180 ft 54 8 m all designs must be verified within PipeIQ software Shipping Weight 8 8 lbs 3 99 kg Net Weight 6 57 lbs 2 98 kg 1 ASUG80001 TABLE OF CONTENTS Items Included With Unit 2 Connectin...

Page 2: ...tructions USB interface cable PipeIQ software comprehensive manual and other helpful documents are available at systemsensor com faast CONNECTING TO FAAST XS FAAST XS requires a valid configuration fr...

Page 3: ...orm the following procedure to mount the unit 1 Before installing the unit onto the bracket remove the appropriate con duit caps from the top or left side of the unit to match the orientation of the w...

Page 4: ...XT MONITOR T8 MODBUS Rx G Rx T9 MODBUS Tx G Tx T10 UNUSED T1 POWER T2 FIRE 2 NC COM NO T3 FIRE 1 NC COM NO T4 ALERT NC COM NO FIGURE 3 POWER AND ALARM CONNECTION BLOCK TABLE 1 TERMINAL DESIGNATIONS AS...

Page 5: ...the following information Detector status Normal Alarm General Fault Isolate Fault Disable Fault Voltage Fault Alarm Level Alert Fire 1 Fire 2 Particulate Level 1 10 relative to Alert Flow level LCD...

Page 6: ...Ds on the right side of the user interface and also on the LCD screen The four Fault LEDs are Fault Isolate Disable Low Voltage 6 ASUG80001 If the General Fault LED is ON the fault condition will be s...

Page 7: ...ME SCREEN 23 JUN 14 10 04AM System Normal 0 0000 ft Menu The menu option is available from the home screen Pressing the select but ton will enter the main menu screen If the device s sounder is active...

Page 8: ...fault or alarm 3 7 RESET The Reset function will reset the device When this function is selected from the functions menu the device will ask for confirmation Use the scroll keys to select cancel or ok...

Page 9: ...ace located in the wiring cabinet of the device The device will validate the configuration before the configuration be comes active After validation of the data the device will perform an initializa t...

Page 10: ...els 10 ASUG80001 for others Table 6 shows the various levels that are available Each Acclimate level is also able to be monitored in PipeIQ This allows the user to read the current Acclimated alarm le...

Page 11: ...TING All FAAST XS systems must be tested after installation and periodically there after Testing methods must statisfy the authority having jurisdiction Systems offer maximum performance when tested a...

Page 12: ...e limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing...

Reviews: