background image

 4 

E56-6001-000 

  

02/16/2018

WIRING

WARNING

Before working on the FAAST XT system, notify all required authorities that 
the system will be temporarily out of service. Make sure all power is removed 
from the system before opening the unit. All wiring must be in accordance 
with local codes.

POWER CABLES

Use the power ratings of the unit to determine the required wire sizes for each 
connection. Use the power ratings of the connected products to determine the 
wire size. 

CONDUIT USAGE

If electrical conduit is used for system wiring, terminate the conduits at the 
cable entry ports on the top or bottom of the unit, using the appropriate con-
duit connectors.
1.   Run all wiring, both power and alarm, through the conduit and into the 

left side of the unit enclosure, as seen in Figure 3.

2.   Attach the appropriate wires to the supplied Euro connector. Follow ap-

propriate local codes and electrical standards for all cabling.

3.  Plug the appropriate connector into the mating connector on the unit.

FIGURE 3. POWER AND ALARM CONNECTION BLOCK

ASP114-01

SYSTEM WIRING

To maintain compliance with EN54-20, the power supply used with FAAST XT 
must be EN54-4 approved. The system requires an EMI line filter in order 
to meet CE certification to CISPR22 specifications. The EMI line filter (in-
cluded) needs to be connected between the DC power supply and the FAAST 
device. The EMI filter needs to be  located within the wiring compartment 
of the FAAST XT unit. Refer to Table 1 for the field wiring terminal descrip-
tions of the unit. Refer to Figure 4 for a typical connection for monitoring the 
FAAST XT system at a Fire Alarm Control Panel (FACP). Refer to your FACP’s 
installation manual for instructions on connecting FAAST XT. 

TABLE 1. TERMINAL DESIGNATIONS

TERMINAL 

BLOCK

T1

External Power – Powers Aspirating Smoke Detector

T2

Not used.

T3

RS 485 Rx 

Rx and Tx can be wired in a half duplex configuration

T4

RS 485 Tx

Rx and Tx can be wired in a half duplex configuration

T5

Alert Relay – Maintains state on loss of power

T6

Action1 Relay – Maintains state on loss of power

T7

Action2 Relay – Maintains state on loss of power

T8

Fire1 Relay – Maintains state on loss of power

T9

Fire2 Relay – Maintains state on loss of power

T10

Minor Fault Relay – Maintains state on loss of power

T11

Urgent Relay – Always reverts to reset on loss of power

T12

Isolate Relay – Maintains state on loss of power

T13

External Monitor 

Summary of Contents for 9400XE FAAST

Page 1: ...R FLOW DISPLAY 6 FAULT DISPLAY 6 LCD USER INTERFACE 7 HOME SCREEN 7 MAIN MENU SCREEN 8 Active Faults 8 Air Flow 8 Functions 8 CONFIGURATION GENERAL SETTINGS 8 Network 9 Email Menu 9 Modbus 9 Alarm Set...

Page 2: ...ary audible indicator ITEMS INCLUDED WITH UNIT FAAST XT unit Mounting bracket and hardware Installation and Maintenance Instructions USB interface cable EMI Filter Assembly PipeIQ software comprehensi...

Page 3: ...e unit to match the orien tation of the wiring See Figure for location of the wiring access plugs 2 Line up the unit with the four mounting clips and the mounting studs on the left side 3 Push the uni...

Page 4: ...power supply used with FAAST XT must be EN54 4 approved The system requires an EMI line filter in order to meet CE certification to CISPR22 specifications The EMI line filter in cluded needs to be co...

Page 5: ...is desired 9 Verify the system fan starts up and air begins to flow out of the exhaust port The user interface will provide the device status 10 The device will establish an airflow baseline during t...

Page 6: ...every 2 seconds The number corresponding to the inlet currently being displayed on the air flow pendulum will be illuminated green The green segments on the air flow pendulum indicate how close the cu...

Page 7: ...isplay under the Active Faults menu The possible fault conditions are as follows TYPE DESCRIPTION ACTIVATED RELAY Low Flow Fault Device has decrease airflow as defined by the user program mable bounda...

Page 8: ...t mode When this function is selected from the functions menu the device will ask for confirmation Use the scroll rs keys to select cancel or ok and then the select 8 key to confirm the selection SOUN...

Page 9: ...TIME OUT The Time Out information set for the unit is displayed DIAGNOSTIC Information on system diagnostics is displayed SPECIAL MODE SCREENS Special mode screens are displayed temporarily when a spe...

Page 10: ...that relay To remove the device from test a RESET must be done SOUNDER TEST The sounder test function can be accessed via the LCD user interface Upon initiation the device will exercise the selected s...

Page 11: ...Ethernet networking equipment Connectivity is provided by an onboard RJ 45 connector located on the bottom of the unit The network interface is required for initial detector configuration Once initial...

Page 12: ...s the authority to increase or alter the obligations or limitations of this Warranty The Company s obligation of this Warranty shall be limited to the repair or replacement of any part of the smoke de...

Reviews: