•If only one leaf is present, the entire sequence must

nevertheless be effected. When the leaf has finished
opening, supply 4 pulses with key 

+

 until the leaf begins

to close, and then resume normal procedure.

5.3 OPERATION WITH GATECODER

By pressing key 

+

 the following functions are pulse-controlled:

1

st

PULSE -Deceleration on opening of leaf 1 (it stops

automatically on reaching the stop limit)

2

nd

PULSE -Leaf 2 opening movement begins

3

rd

PULSE -Deceleration on opening of leaf 2 (it stops

automatically on reaching the stop limit)

4

th

PULSE -Leaf 2 closing movement begins

5

th

PULSE -Deceleration on closing of leaf 2 (it stops

automatically on reaching the stop limit)

6

th

PULSE -Leaf 1 closing movement begins

7

th

PULSE -Deceleration on closing of leaf 1 (it stops

automatically on reaching the stop limit)

8

th

PULSE -Exit learning cycle

The display stops flashing and the gate is ready for normal
operation.

Notes:

•The deceleration pulse should be supplied a little earlier

with respect to the stop limit to prevent the leaf reaching
it at full speed (it would be taken for an obstacle).

•If only one leaf is present, the entire sequence must

nevertheless be effected. When the leaf has finished
opening, supply 5 pulses with key 

+

 until the leaf begins

to close, and then resume normal procedure.

5.4 OPERATION WITH LIMIT-SWITCH AND

GATECODER

When the learning cycle is stated, leaf 1 opens and deceleration
begins when FCA1 operates. The stop limit is recognised
automatically. By pressing key 

+

 the following functions are

controlled by means of the successive pulses:

1

st

PULSE -Leaf 2 starts its opening movement.  The start-of-

deceleration point is commanded by the
intervention of FAC2 and the stop limit is
automatically recognised.

2

nd

PULSE -Leaf 2 starts its closing movement. The start-of-

deceleration point is commanded by the
intervention of FCC2 and the stop limit is
automatically recognised.

3

rd

PULSE -Leaf 1 starts its closing movement. The start-of-

deceleration point is commanded by the
intervention of FCC1 and the stop limit is
automatically recognised.

4

th

PULSE -Exit learning cycle

Notes:

•If some limit-switches  are not installed, start the

corresponding deceleration by pressing key 

+

 (which

replaces the limit-switch).

•If only one leaf is present, the entire sequence must

nevertheless be effected. When the leaf has finished
opening, supply 5 pulses with key 

+

 until the leaf begins

to close, and then resume normal procedure.

6. CONNECTIONS

Inputs 18,19,20,21 of 462 DF are designed for the connection of
opening and closing limit-switches which, according to type of
programming - can command either leaf stop or start of
deceleration. The non-used limit-switches must be jumper
connected (if none are used, this is unnecessary).
Gatecoders can be installed to detect the leaf's angular position
and obtain the electronic anti-crushing function and
deceleration.
The limit-switches and Gatecoders can also be used combined
(for details refer to paragraphs 4.4 and 4.5). To wire, consult fig. 2,3,
and4.

FCA1 - Leaf 1 opening limit-switch

FCC1 - Leaf 1 closing limit-switch

FCA2 - Leaf 2 opening limit-switch

FCC2 - Leaf 2 closing limit-switch

N.B.:

Maximum configurations are shown on the drawings. All
intermediate configurations are allowed, using only some
elements (only 1 Gatecoder, only 1 limit-switch, 2
Gatecoders and 2 limit-switches etc.).

fig.2

fig.3

fig.4

Summary of Contents for Digiprogam

Page 1: ...houttimelearning LEAF1CLOSINGDELAY Delaysclosingstartofleaf1withrespecttoleaf2 Programmable from to minutes for the adjustmentmode seePausetime LEAF2FORCE AdjuststhrustofMotor2 Programmable from minim...

Page 2: ...ht from to Timed output CLOSINGPHOTOCELLSREVERSEONRELEASE Enablethisfunctionifyouwanttheclosingphotocells tostopmovementandreverseitonrelease Default settingisimmediatereverse Active Disabled ASSISTAN...

Page 3: ...set by the 462DF board 4 4 OPERATION WITH LIMIT SWITCH AND GATECODER The motors stop automatically when the opening limit switch is reached The display returns to stand by mode and the gate is ready...

Page 4: ...ve pulses 1st PULSE Leaf 2 starts its opening movement The start of deceleration point is commanded by the intervention of FAC2 and the stop limit is automatically recognised 2nd PULSE Leaf 2 starts i...

Page 5: ...d no effect OPEN CLOSE disabledi LOGIC E PULSES Effects on other active pulse inputs in brackets 1 If the cycle began with OPEN B released leaf an OPEN A pulse will activate both leaves to open Logic...

Page 6: ...es to open no effect closing disabled SAFETY OP CL no effecf OPEN disabeld blocks movement no effect OPEN CLOSE disabledi blocks movement no effect OPEN CLOSE disabledi GATE STATUS CLOSED OPENING OPEN...

Page 7: ...N CLOSE disabledi LOGIC C PULSES COMMANDS ALWAYS PRESSED Effects on other active pulse inputs in brackets 1 If the cycle began with OPEN B released leaf an OPEN A pulse will activate both leaves to op...

Page 8: ...blocks movement no effect OPEN CLOSE disabledi GATE STATUS CLOSED OPENING OPEN ON PAUSE CLOSING BLOCKED LOGIC SP Effects on other active pulse inputs in brackets 1 If the cycle was started with OPEN B...

Reviews: