5.4.2.

J7 Terminal board - Power supply (fig. 23)

POWER SUPPLY (terminals PE-N-L):

PE:

Earth connection

N :

Power supply  ( Neutral )

L :

Power supply  ( Line )

NB.:

 For correct operation, the board must be connected to

the earth conductor in the system. Install an adequate
differential thermal breaker upstream of the system.

To install several partial opening pulse generators,
connect the N.O. contacts in parallel (fig.35).

FSW OP - Opening safety devices contact (terminal 3):

 The

purpose of the opening safety devices is to protect the
leaf movement area during opening. During opening, in
the 

A-AP-S-E-EP

 logics the safety devices reverse the

movement of the gate, or stop and restart the movement
when it is released (see advanced  programming in
Chpt. 5.5.2). During the opening cycle in logicsthe 

B, C

and 

B/C

, they interrupt movement. They never operate

during the closing cycle.
If the 

Opening safety devices 

are engaged when the

gate is closed, they prevent the opening movement.
To install several safety devices, connect the N.C.
contacts in series (fig.25).

NB.: If no opening safety devices are connected, jumper
connect inputs FSW OP and -TX FSW

 (fig. 26).

FSW CL - Closing safety devices contact (terminal 4):

 The

purpose of the closing safety devices is to protect the
gate movement area during closing. During closing, in
the 

A-AP-S-E-EP

 logics, the safety devices reverse the

movement of the gate, or stop and reverse the
movement when it is released (see advanced
programming in Chpt. 5.5.2). During the closing cycle in
logics 

B, C

 and 

B/C

, they interrupt movement. They

never operate during the opening cycle. If the 

Closing

safety devices

 are engaged when the gate is open,

they prevent the closing movement.
To install several safety devices, connect the N.C.
contacts in series (fig.25).

NB.: If no closing safety devices are connected, jumper
connect terminals FSW CL and -TX FSW

 

(fig. 26).

STOP

 

- STOP contact (terminal 5):

 any device (e.g. a push-

button) which, by opening a contact, stops gate
movement.
To install several STOP devices, connect the N.C.
contacts in series (fig. 25).

NB.:

 If STOP devices are not connected, jumper

connect the 

STOP

 and 

-

 terminals.

SAFE -

EDGE safety device contact (terminal 6):

 The purpose of

the "edge" safety device is to protect the leaf movement
area during opening/closing.  In all logics, during opening
and closing, the safety device reverses gate  movement
for 2 seconds. If the safety devices operate again during
the 2-seconds reversing time, it stops movement (STOP)
without any reversing.
If the 

Edge safety device

 is engaged while the gate is

closed or open, it  prevents  movement.
To install several safety devices, connect the N.C.
contacts in series (fig.25).

NB.: If edge safety devices are not connected, jumper
connect the SAFE and - inputs

 (fig. 26).

Negative for power supply to accessories (terminals 7
and 8)

+

24 Vdc - Positive for power supply to accessories
(terminals 9 and 10)

Important: 

Accessories max. load is 500 mA. To calculate

absorption values, refer to the instructions for individual
accessories.

Connection of a pair of closing photocells and a pair of

opening/closing photocells

Connection of two N.O. contacts in parallel

(e.g.  Open A, Open B)

5.4.3.

J6 Terminal board - Motors and flashing lamp
(fig. 23)

MOTOR  - (terminals MOT-C, MOT-1, MOT-2):

 Motor connection

(see Par. 6.5).

LAMP  - (terminals LAMP L, LAMP N)

: Flashing lamp output 230Vac

max 60W.

5.4.4.

J1 Terminal board  - Accessories (fig. 23)

Consult the relevant tables for a detailed description of
operation in the different logics

OPEN A - “Total Opening” command (terminal 1):

 any pulse

generator (push-button, detector, etc.) which, by
closing a contact, commands total opening and/or
closing of the gate leaf.

To install several total opening pulse generators,
connect the N.O. contacts in parallel (fig. 35).

OPEN B - “Partial opening” or “Closing” command (terminal 2):

any pulse generator (push-button, detector, etc.)
which, by closing a contact, commands partial
opening and/or closing of the gate leaf. In the 

B, C

and

 B/C

 logics, it always commands gate closure.

Summary of Contents for 780D

Page 1: ...ta 100 per la natura for nature recycled paper 100 ist umweltfreundlich 100 Altpapier para la naturaleza 100 papel reciclado papier recyclÈ 100 pour la nature voor de natuur 100 kringlooppapier 844ER 780D 844ER 780D ...

Page 2: ... tripping threshold must be checked as specified in the Standards indicated at point 10 16 The safety devices EN 12978 standard protect any danger areas against mechanical movement Risks such as crushing dragging and shearing 17 Use of at least one indicator light e g FAACLIGHT is recommended for every system as well as a warning sign adequately secured to the frame structure in addition to the de...

Page 3: ...torweight Kg Protectionclass Gatemax weight Kg Gatespeed m min Gatemax length m time out Clutch twin diskinoilbath Protectivetreatment cataphoresis Standard equipment Limit switch MSLorinductive Gearmotor overall dimensions LxHxD mm see Fig 2 Electricmotortechnicalspecifications RPM Power W Absorbed current A Starting capacitor µF Power supply Vac 6 10 50 60Hz Tab 1 TECHNICAL SPECIFICATIONS OF 844...

Page 4: ...talimpact Checkifanefficientearthingisavailableforconnectiontothe gearmotor 4 2 MASONRYFORFOUNDATIONPLATE 1 Assemblethefoundationplateasshowninfigure4 2 Thefoundationplatemustbelocatedasshowninfigure5 right closing orfigure6 leftclosing toensuretherackandpinion meshcorrectly 3 Prepare a foundation plinth as shown in fig 7 and wall the foundation plate supplying one or more sheaths for routing elec...

Page 5: ...ing a piece of rack as shown in figure 16 to synchronise the teeth of the two elements 6 Move the gate manually and weld the three threaded pawls thus proceeding until the gate is fully covered 4 4 2 STEEL RACK TO SCREW Fig 14 1 Manually take the leaf into its closing position 2 Lay the first piece of rack level on the pinion and place the spacer between the rack and the gate positioning it at the...

Page 6: ...as follows 4 5 2 MOD 844 ER RF Figs 20 21 1 Insert the spring pin on the shaft using a hammer 2 Fit the idle transmissions bracket on the gearmotor flange using the four screws M5 x 12 and the appropriate washers in the kit as shown in Fig 20 3 Fit the chain pinion on the shaft making the pinion seats coincide with the spring pin and tighten the screw and the appropriate washers and 4 Pass the cha...

Page 7: ...4 1 min Thrust force Adjustable over 50 levels Terminal board inputs Open Partial Open Opening safety devices Closing safety devices Stop Edge Power supply Earth On connector inputs Opening and closing limit switch Motorcapacitor Terminal board outputs Flashing lamp Motor 24 Vdc accessories power supply 24Vdcindicator light Timedoutput Electriclockcommand traffic lights Failsafe Rapid connector 5 ...

Page 8: ...ppedduringthegateopening and closing movements They cause immediate reversal of motion and stopping after two seconds Encoder it is tripped if there is an obstacle during gate opening and closing movements It causes immediate reversal of motion and stopping after two seconds N B If two or more safety devices have the same function opening closing opening and closing edge the contacts must be conne...

Page 9: ...g 33 Fig 32 Fig 29 Connection of a pair of closing photocells Connection of a pair of opening photocells Connection of a pair of opening photocells a pair of closing photocell and an edge safety device Connection of a pair of closing photocells a pair of opening photocells and a pair of opening closing photocells Connection of two pairs of closing photocells and two edge safety devices ...

Page 10: ...fig 26 STOP STOP contact terminal 5 any device e g a push button which by opening a contact stops gate movement To install several STOP devices connect the N C contacts in series fig 25 NB If STOP devices are not connected jumper connect the STOP and terminals SAFE EDGE safety device contact terminal 6 The purpose of the edge safetydeviceistoprotecttheleafmovement areaduringopening closing Inalllo...

Page 11: ... 23 ref to the equipment 5 5 PROGRAMMING To program operation of the automated system access the PROGRAMMING mode with keys F and and using the display on the equipment Attention before attempting to power up the system we advise you to re position the equipment s cover to avoid coming into contact with high voltage parts and to use the push buttons on the cover to activate the keys fig 39 BASICPR...

Page 12: ...Ifthisfunctionisactivated itenablesafunction test of the photocells before any gate movement If the test fails photocells not serviceable signalled by value on the display thegatedoesnotstartmoving Active Disabled PRE FLASHING 5s Activatestheflashinglampfor5secondsbefore startofmovement Disabled Only before opening Only before closing Before every movement CLOSINGPHOTOCELLSLOGIC Select the trippin...

Page 13: ...revs thus obtaininggreaterdecelerationprecision Deceleration disabled from to Deceleration enabled Post limitswitchDECELERATION You can select gate deceleration after the openingandclosinglimit switcheshavebeen tripped Time can be adjusted from to in 0 1 secondsteps If an encoder is used the adjustment is not determined by time but by motor revs thus obtaininggreaterdecelerationprecision Decelerat...

Page 14: ...onecompletecycleoftheautomatedsystem The distance between the limit switch and magnets must befrom 5 to 12 mm Magnets should be fitted on the rack and not on the fixing screws If necessary position the magnet at the side of the screw and adjust decelerations parag 5 5 2 in order to obtain the correct stop point 6 3 DETERMINING THE STOP POINTS AT TRAVEL LIMIT Operator 844 has a limit sensor switch ...

Page 15: ...Commandactivated Commandinactive FC1 Limit switchfree Limit switchengaged FC2 Limit switchfree Limit switchengaged FSWOP Safetydevicesdisengaged Safetydevicesengaged FSWCL Safetydevicesdisengaged Safetydevicesengaged STOP Commandinactive Commandactivated SAFE Safetydevicesdisengaged Safetydevicesengaged ENC Flasheswhilethemotorrotates NB ThestatusoftheLEDswhilethegateisclosedatrestareshowninbold I...

Page 16: ...d to house with the aid of a DIN bar the CN 60E control unit of the safety conductive edge Cut the DIN bar to measure and secure it to the operator with two screws in the appropriate holes and attach the CN 60E control unit to it Fig 50 Forconnectionandoperation refertothespecificinstructions Fig 52 Fig 51 11 INSTALLING REMOTE BOARD 578D If you prefer to install the control board separately from t...

Page 17: ... boards and connectors from the board Unscrew the 3 securing screws of the board and the 2 of the transformer Lift the unit up and gently remove the transformer from the couplings on the board as shown in Fig 53 14 2 OIL TOP UPS Periodically check oil level inside the operator A once a year check is enough for medium or low use frequency For heavier duty every 6 months is recommended To access the...

Page 18: ... i t n o c e s a e l e r n o d n a s k c o L g n i n e p o 2 2 r o f e s o l c o t s e s r e v e R D E K C O L 3 f a e l e h t s e s o l C t c e f f e o N d e l b a s i d N E P O t c e f f e o N t c e f f e o N d e l b a s i d N E P O Tab 3 c E c i g o L S E S L U P S U T A T S E T A G A N E P O B N E P O P O T S S E C I V E D Y T E F A S G N I N E P O S E C I V E D Y T E F A S G N I S O L C E C I...

Page 19: ...o f n e p o o t s e s r e v e R G N I N E P O n o i t a r e p o s p o t S n o i t a r e p o s p o t S d e l b a s i d A N E P O t c e f f e o N 2 2 r o f e s o l c o t s e s r e v e R Tab 3 f B c i g o L S E S L U P S U T A T S E T A G g n i n e p o A N E P O g n i s o l c B N E P O P O T S S E C I V E D Y T E F A S G N I N E P O S E C I V E D Y T E F A S G N I S O L C E C I V E D Y T E F A S L C ...

Page 20: ...s an opening command by radiocontrol or from another suitable device it activates the motor until the opening position is reached If automatic operating mode was set the gate re closes automatically after the selected pause time has elapsed If the semi automatic mode was set a second pulse must be sent to close the door again An opening pulse during re closing always causes movement to be reversed...

Page 21: ......

Page 22: ...pen van de apparaat gehandhaafd blijven zonder zich daardoor te verplichten deze publicatie bij te werken Timbro del Rivenditore Distributor s Stamp Timbre de l Agent Fachhändlerstempel Sello del Revendedor Stempel van de dealer FAAC S p A Via Benini 1 40069 Zola Predosa BO ITALIA Tel 051 61724 Fax 051 758518 www faacgroup com FAAC per la natura La presente istruzione è realizzata al 100 in carta ...

Reviews: