Fig. 14
Connection of two N.O. contacts in parallel
(e.g. Open A, Open B)
Fig. 11
Connection of two pairs of closing photocells and two
edge safety devices
1
2
5
4
3
1
2
RX CL1
TX CL1
1
2
5
4
3
1
2
RX CL2
TX CL2
-
+
-
+
24
V
1 2 3 4 5 6 7 8 9 10 11 12
EDGE
W.L.
TX-F
SW
+
STOP
+
-
-
OPEN
B
A
OPEN
FSW
OP
FSW
CL
Connection of a pair of closing photocells and a pair of
opening/closing photocells
Connection of a pair of closing photocells, a pair of opening
photocells and a pair of opening/closing photocells
Fig. 12
1
2
5
4
3
1
2
RX CL
TX CL
1
2
5
4
3
1
2
RX OP/CL
TX OP/CL
-
+
-
+
1
2
5
4
3
1
2
RX OP
TX OP
-
+
-
+
24V
1 2 3 4 5 6 7 8 9 10 11 12
EDGE
W.L.
TX-F
SW
+
STOP
+
-
-
OPEN
B
A
OPEN
FSW
OP
FSW
CL
1
2
5
4
3
1
2
RX CL
TX CL
1
2
5
4
3
1
2
RX OP/CL
TX OP/CL
-
+
-
+
24
V
1 2 3 4 5 6 7 8 9 10 11 12
EDGE
W.
L.
TX-
FSW
+
STOP
+
-
-
OPEN
B
A
OPEN
FSW
OP
FSW
CL
4.2. J7 Terminal board - Power supply (fig. 2)
POWER SUPPLY (terminals PE-N-L):
PE:
Earth connection
N :
Power supply ( Neutral )
L :
Power supply ( Line )
NB.:
For correct operation, the board must be connected to the
earth conductor in the system. Install an adequate differential
thermal breaker upstream of the system.
4.3. J6 Terminal board - Motors and flashing lamp (fig. 2)
MOTOR - (terminals 13-14-15):
Motor connection.
In gearmotors with a built-in control unit, this connection is pre-
wired standard. For leaf opening direction, see basic
programming in Chpt 5.1.
LAMP - (terminals 16 -17):
Flashing lamp output.
4.4. J1 Terminal board - Accessories (fig. 2)
OPEN A - "Total Opening" command (terminal 1):
any pulse
generator (push-button, detector, etc.) which, by closing
a contact, commands total opening and/or closing of the
gate leaf.
To install several total opening pulse generators, connect
the N.O. contacts in parallel
(see fig. 14).
OPEN B - "Partial opening " or "Closing" command (terminal
2):
any pulse generator (push-button, detector, etc.)
which, by closing a contact, commands partial opening
and/or closing of the gate leaf. In the
B
and
C
logics, it
always commands gate closure.
To install several partial opening pulse generators, connect
the N.O. contacts in parallel (see fig. 14).
Fig. 13