background image

14

19

18

16 17

15

14

12 13

10 11

8 9

6 7

4 5

2 3

1

OPEN 

A

STOP

LOOP 

1

LOOP 

2

LOOP 

2

LOOP 

1

CLOSE

FSW

EMERGENCY

OUT 

1

OUT 

2

OUT 

4

OUT 

3

GND

GND

GND

+24 

V

+24 

V

OUT 

3

J1

19

18

16 17

15

14

12 13

10 11

8 9

6 7

4 5

2 3

1

OPEN 

A

STOP

LOOP 

1

LOOP 

2

LOOP 

2

LOOP 

1

CLOSE

FSW

EMERGENCY

OUT 

1

OUT 

2

OUT 

4

OUT 

3

GND

GND

GND

+24 
V

+24 
V

OUT 

3

J1

4.2.  J1 TERMINAL-BOARD - ACCESSORIES (FIG.2)

LOOP 1 - Power supply to loop1 (OPEN - terminals 1-2): 

use these 

terminals to connect the loop you wish to use as an OPEN pulse 
generator.

LOOP 2 - Power supply to loop2 (SAFETY/CLOSE - terminals 3-4): 

connect between these terminals the loop you wish to use as a 

SAFETY/CLOSE pulse generator.

OPEN - “Opening” Command (N.O. - terminal 5):

 this refers to any 

pulse generator (e.g.: push-button) which, by closing a contact, 

commands the barrier to open and/or close.

  To  install  several  total  opening  pulse  generators, 

connect the N.O. contacts in parallel (see fig. 4)

CLOSE - “Closing” Command (N.O. - terminal 6): 

this refers to any 

pulse generator (e.g.: push-button) which, by closing a contact, 
commands the barrier to close.

  To  install  several  total  opening  pulse  generators, 

connect the N.O. contacts in parallel (see fig. 4)

FSW - Closing safety-devices contact (N.C. -. terminal 7)

 The purpose 

of the closing safety devices is to protect the barrier movement 
area during closure, by reversing motion. They are never tripped 
during  the  opening  cycle.  If  the 

closing  safety  devices

  are 

engaged  when  the  automated  system  is  in  open  status,  they 
prevent the closing movement.

  To install several closing safety devices, connect the 

N.C. contacts in series(fig. 3).

 

If closing safety devices are not connected, jumper 
connect the FSW and FAIL SAFE terminals (fig. 8).

STOP

 

- STOP contact (N.C. -  terminal 8):

 this refers to any device 

(e.g.: push-button ) which, by opening a contact, can stop the 
motion of the automated system.

  To  install  several  STOP  devices,  connect  the  N.C. 

contacts in series (fig. 3.).

 

If stop safety devices are not connected, jumper 
connect the STOP and GND terminals (fig. 8).

EMERGENCY - EMERGENCY contact (N.C. - terminal 9)

 this refers to 

any switch which, by being activated in emergency state, opens 
the barrier and stops its movement until the contact is restored.

 

 

If emergency safety devices are not connected, 
jumper  connect  the  EMERGENCY    and  GND 
terminals (fig. 8).

GND    (teminals  10-11-19)  -  Negative  contact  for  feeding 

accessories

24  Vdc  (terminals  12-13)  -  Positive  contact  for  feeding 

accessories

  Max. load of accessories: 500 mA. To calculate 

absorption  values,  refer  to  the  instructions  for 
individual accessories.

OUT 1 - Outout 1 (terminal 14): 

the output can be set to one of the 

functions described in 2

nd

 level Programming (see parag. 5.2). 

The default value is FAILSAFE. 

OUT 2 - Output 2 (terminal 15): 

the output can be set to one of the 

functions described in 2

nd

 level Programming (see parag. 5.2). 

The default value is beam CLOSED. 

OUT 3 - Output 3 (terminal 16-17): 

the output can be set to one of 

the functions described in 2

nd

 level Programming (see parag. 

5.2). The default value is INDICATOR LIGHT.
Connect  24  Vdc  -  3  W  max.  indicator  light  ,  if  any,  to  these 

terminals, following the instructions in fig. 2.

 

 To  avoid  endangering  correct  operation  of  the 

system, do not exceed the indicated power.

OUT 4 - Output 4 (terminal 18): 

the output can be set to one of the 

functions described in 2

nd

 level Programming (see parag. 5.2). 

The default value is Beam LIGHTED.

Connection of one safety device

Connection of no device with NC contacts.

Fig. 7

Fig. 8

4.3.  J2 TERMINAL-BOARD -  MOTOR - FLASHING LIGHT AND 

FAN (FIG.2)

M (COM-MOT1-MOT2):

 Motor connection

LAMP (LAMP-COM): 

Flashing light output ( 230 V ~)

FAN (FAN-COM): 

Fan output ( 230 V ~)

4.5.  J9 TERMINAL-BOARD - POWER SUPPLY (FIG.2)

PE  :

  Earth connection

N  : 

Power supply 230 V~ ( Neutral )

L  : 

Power supply 230 V~ ( Line )

 

  To ensure correct operation, the board must be 

connected to the earth conductor in the system. 
Install an adequate differential thermal breaker 
upstream of the system.

4.4.  J8 CONNECTOR - MOTOR CAPACITOR (FIG.2)

Rapid connector for connecting the motor thrust capacitor.

Summary of Contents for 624 BLD

Page 1: ...624BLD...

Page 2: ...tain an adequate level of safety the Standards mentioned above must be observed in addition to national legal regulations 11 Before attempting any job on the system cut out electrical power 12 The mai...

Page 3: ...n 50 levels Terminal board inputs Loop1 Loop2 Open Close Closing safety devices Stop Emergency Power supply 230Vac Earth Connector inputs Opening and closing limit switch Detector Motor capacitor Beam...

Page 4: ...the barrier closingmovement and therefore aresuitableforprotecting the closing zone against the risk of impact If two or more safety devices NC contacts have to be connected put them in series with e...

Page 5: ...s fig 3 If stop safety devices are not connected jumper connect the STOP and GND terminals fig 8 EMERGENCY EMERGENCY contact N C terminal 9 this refers to any switch which by being activated in emerge...

Page 6: ...ously press keys and F and hold them down for 5 seconds The following table indicates the sequence of functions accessible in 1ST LEVEL PROGRAMMING 5 PROGRAMMING To program the operation of the automa...

Page 7: ...of the movement Y Active no Excluded Y PF PRE FLASHING to activate the flashing light for 5 sec be fore the start of the movement no excluded OC before every movement CL before closing PA at end of p...

Page 8: ...ng limit switch free Closing limit switch engaged DL8 PIVOT Beam attached Beam detached Display Function Default P1 OUTPUT 1 polarity for configuring the output polarity status Y N C polarity no N O p...

Page 9: ...ediately at end of opening no effect closes immediately at end of opening OPEN IN PAUSE recharges pause time closes stops operation closes recharges pause time closes CLOSING reverses immediately at o...

Page 10: ...tops operation no effect no effect closes immediately at end of opening OPEN IN PAUSE recharges pause time closes stops operation recharges pause time closing disabled recharges pause time closes CLOS...

Page 11: ...ING no effect reverses immediately at closing stops operation no effect no effect no effect OPEN IN PAUSE recharges pause time closes stops operation recharges pause time closing disabled recharges pa...

Page 12: ...sich das Recht vor ohne die wesentlichen Eigenschaften dieses Ger tes zu ver ndern und ohne Verbindlichkeiten in Bezug auf die Neufassung der vorliegenden Anleitungen technisch bzw konstruktiv kommerz...

Reviews: