RP / RP2

624BLD

J4

4.9.  J4 QUICK FIT CONNECTOR -  FOR MINIDEC, DECODER AND RP

It  is  used  for  rapid  connection  of  Minidec,  Decoder  and  RP/RP2 
Receivers.
If you are using an RP2 twin-channel receiver, you will be able to 
directly command the automated system’s OPEN and CLOSE from 
a twin-channel radio control.
If  using  a  single-channel  RP  type  receiver,  only  OPEN  can  be 
commanded.
Fit  the  accessory  with  the  components  side  directed  toward  the 
board interior.

  Insert and remove the boards ONLY after cutting 

power.

4.6.  J3, J5 RAPID CONNECTORS - FOR OPENING AND CLOSING 

LIMIT-SWITCHES (FIG.2)

Quick-fit connector for connection of the opening (13) and closing 
(J5) limit-switches.

4.7.  J6 CONNECTOR - BEAM BREAKING SENSOR (FIG: 2)

Quick-fit  connector  for  connecting  the  beam  breaking  sensor 
(where present). If this sensor is absent, leave the supplied jumper 
in place.

4.8.  J11A,B,C  CONNECTOR  -  QUICK-FIT  CONNECTOR  FOR 

EXTERNAL LOOP DETECTOR (FIG.2)

Quick-fit connector for connecting the external loop-detector. For 
adjustment and programming consult the relevant instruction.

An example of a 624BLD radio accessory connection

  modification  of  the  programming  parameters  is 

immediately effective, whereas definitive memory-
storage  occurs  only  on  exiting  programming  and 
returning to the view of the automation status. If you 
cut power to the unit before returning to view the 

status, all the modifications made will be lost.

  You can return to viewing the status from any point 

of programming at any level, by pressing keys 

F

 and 

-

 simultaneously.

  To  restore  the  programming  default  settings, 

simultaneously press keys 

+

,

-

 and 

F

 and hold them 

down for 5 seconds.

The following table indicates the sequence of functions accessible 
in 1

ST

 LEVEL PROGRAMMING:

5.  PROGRAMMING

To program the operation of the automated system, you must access 
the “

PROGRAMMING

” mode. 

Programming is in two parts: 

1

st

 LEVEL and 2

nd 

LEVEL

5.1.  1

ST

 LEVEL PROGRAMMING

To access 1

ST

 LEVEL PROGRAMMING, use push-button 

F

:

•  if you press it (and hold it down), the display shows the name 

of the first function.

•  if you release the push-button, the display shows the value of 

the function, which can be changed with keys 

+

 and 

-

.

•  if you press 

F

 again (and hold it down), the display shows the 

name of the next function, etc.

•  when  you  reach  the  last  function,  press  the 

F

  push-button 

to exit programming, and the display resumes showing the 
inputs status.

Fig. 9

1

ST

 LEVEL PROGRAMMING

Display

Function

Default

LO

FUNCTION LOGICS:

A

 

Automatic

A1

 

Automatic 1

E

 

Semi-automatic

P

 

Parking

PA

 

Parking Automatic

Cn

 

Condo

CA

 

Condo Automatic

rb

 

Faac-City (traffic bollard logic)

C

 

Dead-man

r

 

Remote

Cu

 

Custom

E

PA

PAUSE TIME:

This  operates  only  if  an  automatic  logic 
was selected. Can be adjusted from 

0

 to 

59

 in one second steps.

Next, the viewing changes in minutes and 
tenths of a second (separated by a dot) 
and time is adjusted in 10 second steps, 
up  to  the  maximum  value  of

 

4.1

  minu-

tes.
E.g.  if  the  display  shows 

2.5

,  the  pause 

time will be 2 min and 50 sec.

20

FO

POWER:

adjusts motor power.

 

0 1

 

minimum power

 

50

 

maximum power

50

L 1

LOOP 1:

If this function is activated, the loop con-
nected  to  the  Loop1  input  will  have  the 
OPEN function.

 

Y

   

= loop1 active

 

n o

 

= loop1 not active

Attention

: if the function is not activated, loop1 

status will nevertheless be available on one of 

the outputs, if appropriately set (see second le-

vel programming).

no

Summary of Contents for 624 BLD

Page 1: ...624BLD...

Page 2: ...tain an adequate level of safety the Standards mentioned above must be observed in addition to national legal regulations 11 Before attempting any job on the system cut out electrical power 12 The mai...

Page 3: ...n 50 levels Terminal board inputs Loop1 Loop2 Open Close Closing safety devices Stop Emergency Power supply 230Vac Earth Connector inputs Opening and closing limit switch Detector Motor capacitor Beam...

Page 4: ...the barrier closingmovement and therefore aresuitableforprotecting the closing zone against the risk of impact If two or more safety devices NC contacts have to be connected put them in series with e...

Page 5: ...s fig 3 If stop safety devices are not connected jumper connect the STOP and GND terminals fig 8 EMERGENCY EMERGENCY contact N C terminal 9 this refers to any switch which by being activated in emerge...

Page 6: ...ously press keys and F and hold them down for 5 seconds The following table indicates the sequence of functions accessible in 1ST LEVEL PROGRAMMING 5 PROGRAMMING To program the operation of the automa...

Page 7: ...of the movement Y Active no Excluded Y PF PRE FLASHING to activate the flashing light for 5 sec be fore the start of the movement no excluded OC before every movement CL before closing PA at end of p...

Page 8: ...ng limit switch free Closing limit switch engaged DL8 PIVOT Beam attached Beam detached Display Function Default P1 OUTPUT 1 polarity for configuring the output polarity status Y N C polarity no N O p...

Page 9: ...ediately at end of opening no effect closes immediately at end of opening OPEN IN PAUSE recharges pause time closes stops operation closes recharges pause time closes CLOSING reverses immediately at o...

Page 10: ...tops operation no effect no effect closes immediately at end of opening OPEN IN PAUSE recharges pause time closes stops operation recharges pause time closing disabled recharges pause time closes CLOS...

Page 11: ...ING no effect reverses immediately at closing stops operation no effect no effect no effect OPEN IN PAUSE recharges pause time closes stops operation recharges pause time closing disabled recharges pa...

Page 12: ...sich das Recht vor ohne die wesentlichen Eigenschaften dieses Ger tes zu ver ndern und ohne Verbindlichkeiten in Bezug auf die Neufassung der vorliegenden Anleitungen technisch bzw konstruktiv kommerz...

Reviews: