BOARD SETUP
DS 1: SW 4 to SW 12
OPENING DELAY
SW 4
The opening of leaf 2 is delayed after the opening of leaf 1. This is to
avoid that the gate’s leafs interfere with each other during the initial part
of the movement. In case there is only one leaf is has no effect.
0 sec (default)
OFF
2 sec
ON
REVERSE AND LAST STROKE
SW 5
If active, before opening, while the gate is closed, the motors thrust to
close for 2 s to facilitate the release of the electric lock. At closing the
motors are activated for a final stroke after slowdown to facilitate locking
of the electric lock.
inactive (default)
OFF
active
ON
MAX THRUST AT STARTUP
SW 6
With this fuction active the motors work at maximum force at startup
(regardless of the force setting) during the initial phase of the movement.
Useful for heavy leafs
inactive (default)
OFF
active for 3 sec
ON
AUTOMATIC OPENING IN CASE OF PO-
WER FAILURE
SW 7
If active and with the optional backup battery installed, the board will
open the gate after one minute from the power failure and keep it open.
Within the minute wait it’s always possible to open and close the gate
with a command. If the logic used has a pause time the board will close
the gate when the power comes back.
inactive (default)
OFF
active
ON
CLOSING SAFETY LOGIC
SW 8
With this function you can choose the behaviour of the closing safety. With
SW8 OFF the gate movement will be reversed as soon as the safety is active,
with SW8 ON the gate will stop when the safety is active and it will reverse
only when the safety is deactivated again.
immediate reverse (default)
OFF
reverse when cleared
ON
PREFLASHING
SW 9
This function activates the flashing lamp for 5s before the movement
of the gate
inactive (default)
OFF
active for 5 sec
ON
EXTRA SENSITIVITY TO
OBSTACLE DETECTION
SW 10
If active this function allows to have an immediate reverse in case the
gate hits a rigid obstacle. This function increases the safety of the gate
operator, however it can generate unwanted obstacle detections.
inactive (default)
OFF
active
ON
ORANGE TERMINAL FUNCTION
SW 11
If OFF after the second consecutive obstacle detection this output is
activated until the STOP contact is open or the power is cycled
if ON the output can be connected to a warning lamp.
IMPORTANT: for UL325 compliance this switch must be OFF
Audio Alarm (default)
OFF
Warning Lamp
ON
OUT FUNCTION (pin 9)
max 100mA
SW 12
if OFF: use pin 9 as power supply negative for a warning lamp. The
lamp will be active during opening, pause and stop. Flashing during
close, off when the gate is closed
If ON: use pin 9 as power supply negative for the safety photocells.
Before any movement the board will check for the presence of the
safety photocells. If the test fails the gate will not move.
IMPORTANT: for UL325 compliance this switch must be ON
Lamp
OFF
Photocells FAIL SAFE active
ON