DIP – SWITCH 2
Default position: OFF
OFF Position = CONTROLS ENABLED:
the bollard movement controls connected to
terminals 24/25 – 26/27 – 58/59 are in operation.
ON Position = CONTROLS DISABLED:
the bollard movement controls connected to
terminals 24/25 – 26/27 – 58/59 are disabled. If the FAAC CITY bollard does not rise,
you may temporarily disable the external control devices and use the push-button
on the board (START) to carry out the test.
DIP – SWITCH 3:
Default position: OFF
OFF Position = SAFETY DEVICES ENABLED:
the inputs for the safety devices
(terminals 20/21) are enabled. If no safety devices are installed, jumper connect
terminals 20 and 21 to each other.
ON Position = SAFETY DEVICES DISABLED:
the input for the safety devices (terminals
20/21) is disabled. If the FAAC CITY bollard does not rise, you may temporarily
disable the safety devices to check if they are to blame for the fault.
Note:
for the installation of metal mass detection devices, consult the bollard
instructions and those for the individual devices.
DIP – SWITCH 4:
Default position: OFF
OFF Position = TRAVEL LIMIT RISE PRESSURE SWITCH ENABLED:
during the final lifting
stage, the pressure switch symbol is used as a rise limit-switch.
ON Position = TRAVEL LIMIT RISE PRESSURE SWITCH DISABLED:
the function described
above is disabled. The rise command is maintained during time out (it cannot be
modified)