DIP – SWITCH 5:
Default position OFF
OFF Position = REVERSING PRESSURE SWITCH ENABLED:
during the lifting stage, if a
weight of over 50 Kg is detected, this trips the pressure switch, which is used as a
safety device to stop the bollard and return it to its low position.
ON Position = REVERSING PRESSURE SWITCH DISABLED:
the function described
above is disabled. If the FAAC CITY bollard does not rise or, if during the rise stage,
the bollard re-descends for no apparent reason, you may temporarily exclude this
function to check if the pressure switch is to blame for the fault.