KNX 100G Setup

1. Add KNX 100G Interface Within

 

ETS

Within ETS, the KNX 100G interfaces can be selected and setup via “Bus Interfaces”. 

NOTE:

  ETS  can  access  configured  KNX  100G  interfaces  without  a  database  entry  if  the  default  settings  are  compatible  with                                                                                                                                            

the KNX installation. If the KNX 100G setup does not comply with installation conditions, it must be configured within an 
ETS project. See 

Configure Interface Properties on page 4

.

After connecting the KNX 100G to the LAN and the KNX bus, the device should automatically appear in ETS within the “Bus” 
menu under “Discovered Interfaces”. By double clicking on the discovered interface, it will be selected as the current interface. On 
the right side of the ETS window, all specific information and options of the connection appear (see figure 5).

2. Setup Individual Address for Tunneling

The device’s name and “Individual Address” can be changed within your ETS project. The KNX 100G has an individual address 
which can be used to access the device. 

The device supports up to five connections for control. Each connection is associated with one of the five individual addresses 
in the device. The addresses can be assigned via ETS. Telegrams sent to the bus contain a sender address from one of the five 
additional addresses, and response telegrams can be transmitted to respective clients.

Additional individual addresses must be selected from the address range of the bus line in which the interface is installed and may 
not be used by another device. The individual KNX 100G address and the addresses for additional tunneling connections can be 
changed within the ETS project after the device has been added to the project.

Factory Default Settings

Setting

Value

Individual Device Address

15.15.255

Number of configured KNXnet/IP tunneling 
connection

1

Individual address of tunneling connection

15.15.250

IP address assignment:

DHCP

Reset to Factory Device Settings

The following callouts reference

 

Figure 1 on page 1.

1. 

Separate the KNX Bus connector 

A

 from the device.

2. 

Press and hold the Programming Mode button 

B

.

3. 

Reconnect KNX Bus connector 

of device.

4. 

Continue holding the Programming Mode button 

B

 for six seconds.

5. 

A short flashing of all LEDs 

(

CDEF

)

 visaulizes the successful reset of the device to factory default settings. 

Figure 5.      

Changing Device Address in ETS

Figure 4.      

New Connection in Bus Interfaces

Summary of Contents for KNX 100G

Page 1: ...e top rear against wall furniture Figure 2 1 3 Slide the unit down onto top of rail Figure 2 2 4 Tilt the unit and snap onto the rail Figure 2 3 Figure 1 KNX 100G Controls and Displays DIN Rail KNX 100G Patent s www extron com patents 33 2700 01 A E Prog KNX __ __ ____ E Prog __ __ ___ E KNX 100G KNX Mode IP P Esc Conn Up Conn Dn AN 33 255 8 01 B e s t e s t KNX 100G Place top rear against wall fu...

Page 2: ...NX 100G Patent s www extron com patents 33 2700 01 A E E es t es t KNX 100G Patent s www extron com patents 33 2700 01 A E Prog KNX __ __ ____ E KNX 100G KNX Mod e IP P Esc Con n Up Con n Dn Ethernet Twisted Pair Cable IPC P PR O 55 0 OVER 2 1 4 3 LIMIT R IR 1 2 3 4 5 6 7 8 Tx Rx Tx Rx RTS CTS COM IR S ERIA L 1 3 2 4 RELA YS FLEX I O S LIMIT OVER eBU S SWIT CHE D 12 VDC 1000 LINK ACT 2 1 5 6 3 7 4...

Page 3: ...h one of the five individual addresses in the device The addresses can be assigned via ETS Telegrams sent to the bus contain a sender address from one of the five additional addresses and response telegrams can be transmitted to respective clients Additional individual addresses must be selected from the address range of the bus line in which the interface is installed and may not be used by anoth...

Page 4: ...xtfield frame switches to color red after entering the address the address is already taken within your ETS project NOTE Make sure none of the individual KNX addresses are in use within the KNX installation If the physical KNX addresses of the tunneling connections have been assigned via ETS a manual address setting on the device is not allowed The IP network specific options of the KNX 100G can b...

Reviews: