EBP 108 RAAP Button Panel • Setup Guide (Continued)

Step 4: Set BUS ID Addresses

Up to eight devices can be connected to one control processor. In order for the control processor to be successfully configured, 
each device connected to the same control processor must have a unique six-bit, BUS ID, which is set with the DIP switch 
assembly on the rear panel of the EBP (see 

figure 1

C

, on page 1). If two or more modules have the same bus ID, address 

conflicts may cause one or more of the panels to not be recognized by the IPCP Pro control processor. If there is an address 
conflict, the red status LED (

figure 1

D

) lights steadily (see also 

Step 7: Test and Troubleshoot

step 2

 on page 9).

Various combinations of the six DIP switches set to On or Off provide 64 addresses: 

0

 is a reserved eBUS ID and the configurable 

eBUS ID range is 

1

 through 

63

 (see the table on the two following pages). The section below shows an example of binary to 

decimal conversion. 

eBUS ID Setup

Dip Switch

Position
Decimal

Off

1

2

5

=32

2

Off

2

4

=16

5

On

2

1

=2

4

Off

2

2

=4

3

Off

2

3

=8

6

Off

2

0

=1

Slide

1 2 3 4 5 6

ON

M

S

B

L

S

B

BUS ID

Figure 5. 

eBUS ID Setup

Add the decimal numbers for each of the DIP switches that are set to On to obtain the address of the device. In figure 5, only DIP 
switch #5 is on and the rest are off, which means the address for the device in figure 5 is 0+0+0+0+2+0=2.

NOTES:

• 

Any address can be used except address 

0

 (binary: 

000000

), which is reserved as the address of the controller.

• 

Switch 1 (on the left) is the highest value (32, the most significant bit) and is labelled 

MSB

.

• 

Switch 6 (on the right) is the lowest value (1, the least significant bit) and is labelled 

LSB

.

• 

Up

 = On = 

1

Down

 = Off = 

0

The factory default address for the EBP 108 RAAP is 25 (BUS ID = 011001). The ID can be changed to any valid value. 
The table on the following two pages shows the DIP switch settings for all 64 possible addresses.

Replacing the volume control knob

1. 

To remove a knob, firmly grasp the knob and pull it away 
from the EBP. There is no need to remove the faceplate.

2. 

To replace the knob, align the ridge 

inside

 the new knob 

(figure 4, 

1

) with the channel on the knob control (

2

and allow the magnet in the knob to snap into place.

2

1

EBP 108 RAAP Top View

Figure 4. 

Replacing the Volume Control Knob

Summary of Contents for EBP 108 RAAP Button Panel

Page 1: ...figurator Plus and Professional GCP configuration software the Toolbelt utility software or Global Scripter programming software to configure the control processor Once configured the panels can be us...

Page 2: ...ith Global Configurator Plus and Professional or programming with Global Scripter see the software help file for more information C Volume Control LEDs and Rotary Encoder Use the encoder to adjust the...

Page 3: ...use a piece of sticky tape to pull it out of the button cap 4 Select one of the button labels from the printed label sheets included with the unit Remove the label from its backing and remove the cle...

Page 4: ...ff 22 4 3 Off 23 8 6 Off 20 1 Slide 1 2 3 4 5 6 ON M S B L S B BUS ID Figure 5 eBUS ID Setup Add the decimal numbers for each of the DIP switches that are set to On to obtain the address of the device...

Page 5: ...4 5 6 ON M S B L S B 0 0 0 1 0 0 4 1 2 3 4 5 6 ON M S B L S B 0 1 0 0 1 1 19 1 2 3 4 5 6 ON M S B L S B 0 0 0 1 0 1 5 1 2 3 4 5 6 ON M S B L S B 0 1 0 1 0 0 20 1 2 3 4 5 6 ON M S B L S B 0 0 0 1 1 0...

Page 6: ...6 1 2 3 4 5 6 ON M S B L S B 1 1 0 1 0 1 53 1 2 3 4 5 6 ON M S B L S B 1 0 0 1 0 1 37 1 2 3 4 5 6 ON M S B L S B 1 1 0 1 1 0 54 1 2 3 4 5 6 ON M S B L S B 1 0 0 1 1 0 38 1 2 3 4 5 6 ON M S B L S B 1 1...

Page 7: ...source are isolated from the devices powered by the second source by see figure 7 on the following page ATTENTION Always use a power supply supplied or specified by Extron Use of an unauthorized power...

Page 8: ...at is already powered by the IPCP Pro control processor or by an additional power supply 3 16 5 mm Max Tie drain wires to ground EBP 108 RAAP eBUS Connections Connect up to five eBUS endpoint devices...

Page 9: ...is receiving power but communication with the control processor is not confirmed Red LED Lights steadily when there is a BUS ID address conflict Green LED Lights steadily when power and communication...

Page 10: ...gure 1 on page 1 and see Step 5 Cable All Devices on page 7 6 Optional Connect cables to the AAPs Follow the instructions provided with the AAP 7 If you have not already done so set the DIP switches t...

Reviews: