3 - 5%

Max 3 mt

ENGLISH

ExamPlES oF CoRRECt CoNNECtIoN to thE ChImNEy

In the presence of type B gas appliances with intermittent operation not intended for heating, they must have their own aeration and/or 

ventilation opening. 

The air inlets must meet the following requirements:

 

Š

they must be protected with grids, metal mesh, etc., but without reducing the net useful section;

 

Š

they must be made so as to make the maintenance operations possible;

 

Š

positioned so that they cannot be obstructed;

The clean and non-contaminated air flow can also be obtained from a room adjacent to that of installation (indirect aeration and 

ventilation), as long as the flow takes place freely through permanent openings communicating with the outside.

The adjacent room cannot be used as a garage, or to store combustible material or for any other activity with a fire hazard, bathroom, 

bedroom or common room of the building.

flue gas eXhaust

The heat generator works in depression and is equipped with an outlet fan for flue gas extraction. There must be a single exhaust system for 

the generator. Using a flue that is shared with other devices is not allowed.

The components of the flue gas exhaust system must be chosen in relation to the type of appliance to be installed in compliance with:

 

Š

UNI/ TS 11278 in the event of metal chimneys, with particular attention to that stated in the specification; 

 

Š

UNI EN 13063-1 and UNI EN 13063-2, UNI EN 1457, UNI EN 1806 in the event of non-metallic chimneys.

 

Š

The length of the horizontal section must be minimal and, in any case, no longer than 3 metres, with a minimum upward slope of 3%

 

Š

There must not be more than 4 direction changes including the one due to the use of the "T" element.

 

Š

A “T” fitting with a condensation collection cap must be provided at the base of the vertical section.

 

Š

If the exhaust is not inserted in an existing flue, a vertical section with a windproof end piece is required (UNI 10683).

 

Š

The vertical duct can be inside or outside the building. If the smoke duct is inserted in an existing flue, it must be certified for solid fuel.

 

Š

If the smoke duct is outside the building, it must always be insulated.

 

Š

The smoke ducts must have at least one airtight inlet for flue gas sampling.

 

Š

All the sections of the flue gas duct must be accessible to inspection.

 

Š

Inspection openings must be provided for cleaning.

 

Š

If the generator has a fume temperature lower than  160°C+ ambient temperature caused by the high yield (contact technicians) it 

MUST be resistant to humidity.

ChImneY Cap

The chimney caps must meet the following requirements:

 

Š

they must have a useful outlet section no less than double that of the chimney/ducted system on which it is installed;

 

Š

they must be adapted in order to prevent the penetration of rain and snow in the chimney/ducted system;

 

Š

they must be built so that, in the event of winds coming from all directions and from any angle, the expulsion of combustion products 

is in any case ensured;

Protection from rain 

and wind

C o n d e n s a t i o n -

proof "T" fitting with 

inspection plug 

Insulated flue

Insulated "T" 

fitting with 

inspection plug

Protection from rain and wind

"T" fitting with 

i n s p e c t i o n 

plug

ConneCtIon to the maIns eleCtrIC supplY

The generator is supplied with an electric power cable to be plugged into a 230V 50 Hz socket, possibly with a circuit breaker switch. The 

socket must be easily accessible.

The electrical system must be compliant with standards. The efficiency of the earthing circuit must be checked. Unsuitable earthing of the 

system can cause malfunctioning for which the manufacturer will not be held liable. 

Power supply variations beyond 10% can cause faulty operation of the product.

8

Summary of Contents for 001282600

Page 1: ...MADE IN ITALY design production VIRNA IDRO 004276851 rev 002 UK THERMO PRODUCTS USER MANUAL...

Page 2: ...ENGLISH 2...

Page 3: ...hermostat 21 Additional thermostat functioning with STAND BY active 21 Additional thermostat operation with STAND BY deactivated 21 Additional thermostat installation 21 easy setup 22 CHRONO 22 Enabli...

Page 4: ...IMP RATIF Avant de d placer le po le retirer le rev tement indiqu pour viter tout dommage ACHTUNG PFLICHT Bevor der Ofen bewegt wird muss die angezeigte Verkleidung entfernt werden um Sch den zu verme...

Page 5: ...ITH REDUCED PHYSICAL SENSORY OR MENTAL CAPACITIES OR WITHOUT EXPERIENCE OR THE NECESSARY KNOWLEDGE PROVIDED THAT THEY ARE SUPERVISED OR HAVE RECEIVED INSTRUCTIONS ON SAFE USE OF THE APPLIANCE AND THAT...

Page 6: ...r ignition During the filling phase do not put the bag of pellets to into contact with the product The majolicas aretop quality artisan products and as such can have micro dots crackles and chromatic...

Page 7: ...at the documentation has been provided and must keep it with a copy of the technical documentation relating to the installation For installation in a condominium prior approval from the condominium s...

Page 8: ...lection cap must be provided at the base of the vertical section If the exhaust is not inserted in an existing flue a vertical section with a windproof end piece is required UNI 10683 The vertical duc...

Page 9: ...for passive houses because it does not take air in from within the house combustion air To ensure the stove remains hermetically sealed the connection pipe for the combustion air must be directly con...

Page 10: ...and inspection of correct functioning must be carried out perfectly in full compliance with Standards in force national regional and municipal as well as these instructions For Italy installation mus...

Page 11: ...harge into the flue This is to prevent unexpected power increases The flue fitting can be mounted between the boiler and the flue only after this inspection An inspection of the connections with pre e...

Page 12: ...output T3 Boiler return input Virna IDRO details Combustive air rear inlet Lower fumes exhaust Upper fumes exhaust Combustive air side inlet Pellet hopper pressurised closure Heat exchanger scrapers E...

Page 13: ...conveying motor and therefore operation of the heat generator The system must be bled several times to eliminate the air and loaded when the pressure is too low It is not an anomaly but normal phenome...

Page 14: ...gnitionthestovewillgointo DEPRALARM mode while during normal operation the stove will go into COOLING WAITING TIME mode and then re start automatically when the correct conditions are present stove co...

Page 15: ...be seasoned in order to obtain a sufficiently adequate heat yield THE USE OF POOR QUALITY PELLETS OR ANY OTHER MATERIAL DAMAGES THE FUNCTIONS OF THE GENERATOR AND CAN VOID THE WARRANTY AND THE ANNEXED...

Page 16: ...external additional thermostat is closed and the STAND BY function is enabled Flashing with contact open the contact of the external additional thermostat is open and the STAND BY function is enabled...

Page 17: ...must be followed the first times the stove is ignited It is possible that slight odours are produced due to the drying of the paints and silicone used Do not remain in the room for long periods Do not...

Page 18: ...15 Decrease Decreases the value displayed 16 Stove status Displays the general status of the stove Battery type and replacement The battery is housed in the lower part of the remote control To replac...

Page 19: ...d key 1 to return to the previous menus to the initial state Language This menu allows the preferred language to be selected The languages available are Italiano English German French Spanish Portugue...

Page 20: ...d the stove will re start automatically and continue the working phase returning to the selected power level MODULATION and H OFF As the water temperature approaches the set point the boiler starts to...

Page 21: ...inside the stove and relative factory setting restrictions If the stove is in H OFF water temperature reached any additional contact or thermostat request will be ignored Additional thermostat operati...

Page 22: ...ENOUGH Controls procedure Press key 6 Press key 3 until easy setup appears and confirm by pressing key 6 Use keys 4 and 5 to set the range Press key 6 to confirm and key 1 to return to the previous m...

Page 23: ...FF 00 00 PRG1 stop time Monday Sunday On off Enabling disabling days for PRG1 Set prg1 65 C 80 C 149 F 176 F Set thermostat PRG1 Power prg1 1 5 Set power PRG1 prg2 Start prg2 OFF 00 00 PRG2 start time...

Page 24: ...02 00 23 00 08 00 16 30 t 02 00 23 00 08 00 16 30 t 3 1 02 00 23 00 08 00 16 30 t 72 68 2 1 Time slot 1 start 02 00 stop 23 00 power 3 set temp 72 C Time slot 2 start 08 00 stop 16 30 power 1 set tem...

Page 25: ...via an additional thermostat Controls procedure Press key 6 Press key 3 until SETTINGS appears and confirm by pressing key 6 Continue by pressing key 3 until STAND BY appears and confirm by pressing k...

Page 26: ...Press 3 until SETTINGS appears and confirm by pressing 6 Press key 3 until OUTLET AIR appears and confirm by pressing key 6 Use keys 4 and 5 for enabling ON or disabling OFF Press key one several time...

Page 27: ...use abrasive or chemically aggressive detergents for cleaning The ceramic glass must be cleaned when the glass is completely cold To clean the ceramic glass simply use a dry brush and some damp newspa...

Page 28: ...burn pot using the poker supplied Re position the burn pot in its seat and push it towards the fire wall Replace the pellet chute assembly on the burn pot Make sure that the burn pot and pellet chute...

Page 29: ...ENGLISH EVERY 30 DAYS Cleaning the combustion chamber deflector Remove the deflector and eliminate the ash deposited in the upper part of the deflector 29...

Page 30: ...physically and a pellet chute assembly B When cleaning and removing the burn pot remove the pellet chute assembly B by lifting it see figure Perform the same operation in reverse order to re assemble...

Page 31: ...product warranty GASKETS pellet hopper lid DOOR ASH DRAWER AND BURN POT The gaskets guarantee the tightness of the stove and its consequent good functioning They must be controlled periodically They m...

Page 32: ...let hopper ash drawer and door replace them and apply silicone where envisioned C Combustion chamber and heat exchanger full cleaning including ignition plug pipe D Hopper complete emptying and cleani...

Page 33: ...llet hopper ash drawer and door replace them and apply silicone where envisioned C Combustion chamber and heat exchanger full cleaning including ignition plug pipe D Hopper complete emptying and clean...

Page 34: ...it will re start automatically Anti freeze The anti freeze function is in progress as the H2O temperature is below the factory set threshold the pump is active until the water reaches the pre set fact...

Page 35: ...tre MAX H20 PRESSURE ALARM Air in the system Inadequate circulation Possible air in the system bleed the system Lack of adequate circulation Lack of or inadequate safety zone The water in the stove ha...

Page 36: ...ity to use the product and wrong maintenance by the consumer with respect to what is reported and recommended by the instructions manual of the product which is part of the sales contract this guarant...

Page 37: ...t pipes etc Please therefore avoid coming into contact with these parts without wearing suitable protective clothing or using appropriate measures such as heat protective gloves DO NOT use the product...

Page 38: ...ENGLISH 38...

Page 39: ...ENGLISH 39...

Page 40: ...lame it www lanordica extraflame com TO FIND THE SERVICE CENTRE NEAREST TO YOU CONTACT YOUR DEALER OR CONSULT THE SITE WWW LANORDICA EXTRAFLAME COM The manufacturer reserves the right to vary the char...

Reviews: