Additional Installation Tips
20
Beijer Electronics, MAEN966
6.2 Ethernet Connection in the Panel
1. In some industrial units for Ethernet, the RJ45 contact’s shield is connected to
the chassis via a capacitor.
2. The operator panel’s Ethernet shield is directly connected to the chassis.
Check whether the other Ethernet unit has its shield directly grounded or grounded
via a capacitor.
In many cases, connecting the shielded Ethernet cabling to the chassis at both ends
is inappropriate. Hum or grounding loops can occur. Unshielded cabling may even
result in fewer communication errors.
A good solution may be to use a shielded Ethernet cable
,
but to connect the shield at
one end only.
3. One option is to break the shield.
4. A more elegant method is to expand the shielded Ethernet cabling with a piece
of unshielded Ethernet cable.
5. You can ground the shield via an external 0.1 uF/250 V plastic capacitor. This
will connect the HF transients to the ground.
1
2
3
4
5
5351
1-1
2-2
3-3
8-8
Industrial Ethernet
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
Operator panel
Operator panel
Operator panel
Operator panel
Shielded
Short and
unshielded
0.1 uF
250 V
Summary of Contents for EXTER T150sr
Page 1: ...EXTER T150sr Installation Manual MAEN966 2008 11 English...
Page 4: ...Table of Contents Beijer Electronics MAEN966...
Page 8: ...Safety Precautions 8 Beijer Electronics MAEN966...
Page 12: ...Installation 12 Beijer Electronics MAEN966...