Timer (selection 8) in parameter "A1Fu". Set the time to 120 minutes (2 hours) in 
parameter "timE". When the controller is powered the alarm relay will be OFF, when 
the PV = SV the relay remains OFF but the timer begins to countdown, and after 2 
hours the relay will turn ON permitting the process event to take place. 

 

12. RS-485 OPTION 

The optional RS-485 PC interface permits up to 32 controllers to be connected to a PC for 
remote operation. Each controller must have a unique address between 0 and 31 which is 
programmed in parameter "addr". The "remo" parameter must be set to '1' to activate a 
controller’s interface. The RS-485 wiring terminals are shown in Figure 3, Section 4. 
Detailed information is provided with the purchase of the RS-485 option. 

 

13. CUSTOMER SERVICE 

Extech offers complete repair and calibration services

 for all of the products we sell. 

For periodic calibration, NIST certification or repair of any Extech product, call customer 
service for details on services available. Extech recommends that calibration be performed 
on an annual basis to insure calibration integrity. 
 

14. WARRANTY 

EXTECH INSTRUMENTS CORPORATION warrants this instrument to be free of defects 
in parts and workmanship for one year from date of shipment (a limited warranty may 
apply on sensors and cables). If it should become necessary to return the instrument for 
service during or beyond the warranty period, contact the Customer Service Department 
at (781) 890-7440 for authorization. 

A Return Authorization (RA) number must be 

issued before any product is returned to Extech.

 The sender is responsible for 

shipping charges, freight, insurance and proper packaging to prevent damage in transit. 
This warranty does not apply to defects resulting from action of the user such as misuse, 
improper wiring, operation outside of specification, improper maintenance or repair, or 
unauthorized modification. Extech specifically disclaims any implied warranties or 
merchantability or fitness for a specific purpose and will not be liable for any direct, 
indirect, incidental or consequential damages. Extech's total liability is limited to repair or 
replacement of the product. The warranty set forth above is inclusive and no other 
warranty, whether written or oral, is expressed or implied. 
 

Copyright 

©

 1999 Extech Instruments Corporation. All rights reserved 

including the right of reproduction in whole or in part in any form.

 

 

APPENDICES

 

Appendix A:  Alarm Mode Selections for parameters 'A1Fu' and 'A2Fu" 

 

 '00'  Deviation High Alarm

:  For the Deviation High Alarm, the value entered for the 

"A1SP" (Alarm 1 setpoint) or 'A2SP" (Alarm 2 setpoint) parameters equals the 
amount the controller's HIGH alarm setpoint is offset from the main controller 
setpoint. For example, if SV = 400 and A1SP = +10 then the Limit Alarm relay will 
trip when the temperature reaches 410

o

.  The Deviation alarm setpoint tracks the 

main setpoint meaning that it changes as the main setpoint changes always 
remaining a programmed number of units from the main setpoint. 

 

'01'  Deviation Low Alarm: 

With the Alarm setup as a Deviation Low Alarm, the value 

entered for the "A1SP" (Alarm 1 setpoint) or 'A2SP" (Alarm 2 setpoint) parameters 
equals the amount to which the controller's LOW alarm setpoint is offset from the 
main controller setpoint. For example, if you entered  SV = 400 and A1SP = -10 
then the Alarm relay will trip when the temperature falls below 390

o

. The Deviation 

alarm setpoint tracks the main setpoint meaning that it changes as the main 

Summary of Contents for 96VTR

Page 1: ...red setpoint This Three Mode PID controller offers Simultaneous Process Value PV and Setpoint Value SV display Automatic alarm functions 11 in all Autotuning automatically tailors the controller s res...

Page 2: ...emperature 4 to 140 o F 20 to 60 o C Dimensions Cutout 3 58 x 3 58 0 02 91 0 x 91 0mm 0 5mm 2 2 Input Specifications Thermocouple inputs Programmable Types J K T E B R S N Cold Junction Compensation T...

Page 3: ...Manual Reset 0 to 100 of Prop Band Hysteresis 0 0 to 25 5 of Full Scale 3 MOUNTING AND WIRING 3 1 Prepare a 3 58 x 3 58 0 02 91 0 x 91 0mm 0 5mm panel cutout refer to Fig 2 The panel on which the cont...

Page 4: ...which the controller s output s will adjust the process To change the setpoint use the up down arrow keys The setting range equals the range the user selects in the LoLt Low Limit and HiLt High Limit...

Page 5: ...ow each parameter title as you scroll through the list Also to activate an autotuning session press and hold this key for 5 seconds UP Arrow Key Increases the Setpoint SV and increments parameter data...

Page 6: ...Then program the desired limit here Allowable setting range is limited by parameter LoLt and HiLt Low and High Limit settings 7 SECOND PROGRAMMING LEVEL PARAMETERS Press and hold the SCROLL and RETUR...

Page 7: ...cked 14 same as 2 but levels 2 3 4 locked 9 same as 1 w levels 3 4 locked 15 same as 3 but levels 2 3 4 locked A1Fu Alarm 1 Function Select an Alarm Timer function from the function list in Appendix A...

Page 8: ...OFF OFF ON ON 11 ON OFF ON ON 4 OFF ON OFF OFF 12 ON ON OFF OFF 5 OFF ON OFF ON 13 ON ON OFF ON 6 OFF ON ON OFF 14 ON ON ON OFF 7 OFF ON ON ON 15 ON ON ON ON Addr Controller address used with the RS...

Page 9: ...alue which will display when a 4mA signal is applied to the controller For example for a 4 20mA unit to display from 50 to 150 set LoCA to 50 e Press and hold the RETURN key for at least 5 seconds and...

Page 10: ...will extinguish The new Tuning values will now be stored in nonvolatile memory Adjustments can be made manually if desired in programming level 2 e To abort an Auto Tune process simply press and hold...

Page 11: ...s outputs to maintain the desired limit programmed by the user A setting of zero defeats the Ramp to Setpoint function 11 2 Soak Timer Function for use with Alarm 1 only The Alarm 1 Soak Timer allows...

Page 12: ...nce and proper packaging to prevent damage in transit This warranty does not apply to defects resulting from action of the user such as misuse improper wiring operation outside of specification improp...

Page 13: ...e Same as the Process Low Alarm but no relay action takes place until the process PV reaches the setpoint for a second time Standby sequence is also known as Startup Inhibit and is useful for avoiding...

Page 14: ...nding upon the alarm type where no relay action can occur to eliminate relay chatter Act Action This is control output action Set to 1 for heating unit Set to 1 for o F dp decimal point Set to 0 for n...

Page 15: ...which the controller s secondary cooling output is permitted to throttle between 0 and 100 Outside this region the controller s secondary output is either 0 above the band or 100 below the band Figure...

Reviews: