background image

14                                     96VTR      Ver. 2.0   11/99

 

Appendix B: Application Programming Example 

 
(Refer Fig.5).

 

The aim is to maintain an 

oven temperature of 500

o

F. The 

controller monitors the oven temperature 
via the thermocouple. The controller 
compares the actual temperature (PV) to 
the desired temperature (500

o

 setpoint 

SV) and throttles the heater as needed 
to maintain 500

o

F. If the oven 

temperature reaches too high, the 
controller's alarm output can trigger an 
audio or visual alert. The alarm contact 
can also be used to switch on/off an 
external  device such as a master switch 
or cooling fan. In this example, the alarm will trigger an annunciator at 600

o

F.  To program 

the controller to perform the task described above, refer to the steps below. The 
parameters not listed below are either inconsequential with regard to this example or they 
will not appear on the controller display due to the controller configuration. Use the 
programming level sequence shown below (i.e., Level 3 then Level 1. etc.) 

 
Programming Level 3

 

A1Fu 

(Alarm Function): Set to '2' which is an absolute alarm meaning that the alarm is 

fixed. In this case the alarm will be fixed at 600

o

F. This 600

o

F value is 

programmed later in the procedure. 

A1HY

 (Alarm Hysteresis): Set to '0'. Hysteresis is similar to 'deadband'. A region 

extending from the alarm setpoint up or down, depending upon the alarm type, 
where no relay action can occur to eliminate relay chatter. 

Act

 (Action): This is control output action. Set to '1' for heating. 

unit: 

Set to '1' for 

o

dp 

(decimal point): Set to '0' for no decimal point 

Ct 

(Cycle time):

 

To start off with, set to approx. 6 seconds. This can be re-adjusted later 

after the process is observed. Cycle time is the rate at which the controller will 
make adjustments to the heater. Set for the longest time possible (to save relay 
life) without causing process oscillations.  

tYPe:

 Set to '1' for a K Type Thermocouple

 

LoLt and HiLt

 (Low Limit / High Limit): Set these to 0

o

 and 1000

o

 respectively. This is 

simply a span setting. 

Programming Level 1

 

A1SP

 (Alarm Setpoint): Set to 600

o

F. Temperature at which the alarm relay will switch on the 

alert annunciator. 
 

Tuning the Controller (Level 2 parameters)

 

The best plan of attack with tuning is running the Auto Tune utility. Auto Tune will 
automatically program the controller to respond with little process oscillation around 
setpoint and minimal overshoot on oven heat-up. Run the Auto Tune utility per section 9.2 
in this manual. Running Auto Tune supersedes programming Level 2 parameters. 

 
Calibration (Level 4 parameters)

 

Calibration is very rarely required. If calibration must be performed refer to Section 9.1 for 
details or contact Extech. 

Heater

Oven

96VTR

K Thermocouple input

Control Output

Compares oven

temperature with
desired setpoint

and adjusts heater

(Adjusts Heater)

(Measures oven temp.)

Alarm Annunciator

Alarm Output

Figure 5

Summary of Contents for 96VTR

Page 1: ...red setpoint This Three Mode PID controller offers Simultaneous Process Value PV and Setpoint Value SV display Automatic alarm functions 11 in all Autotuning automatically tailors the controller s res...

Page 2: ...emperature 4 to 140 o F 20 to 60 o C Dimensions Cutout 3 58 x 3 58 0 02 91 0 x 91 0mm 0 5mm 2 2 Input Specifications Thermocouple inputs Programmable Types J K T E B R S N Cold Junction Compensation T...

Page 3: ...Manual Reset 0 to 100 of Prop Band Hysteresis 0 0 to 25 5 of Full Scale 3 MOUNTING AND WIRING 3 1 Prepare a 3 58 x 3 58 0 02 91 0 x 91 0mm 0 5mm panel cutout refer to Fig 2 The panel on which the cont...

Page 4: ...which the controller s output s will adjust the process To change the setpoint use the up down arrow keys The setting range equals the range the user selects in the LoLt Low Limit and HiLt High Limit...

Page 5: ...ow each parameter title as you scroll through the list Also to activate an autotuning session press and hold this key for 5 seconds UP Arrow Key Increases the Setpoint SV and increments parameter data...

Page 6: ...Then program the desired limit here Allowable setting range is limited by parameter LoLt and HiLt Low and High Limit settings 7 SECOND PROGRAMMING LEVEL PARAMETERS Press and hold the SCROLL and RETUR...

Page 7: ...cked 14 same as 2 but levels 2 3 4 locked 9 same as 1 w levels 3 4 locked 15 same as 3 but levels 2 3 4 locked A1Fu Alarm 1 Function Select an Alarm Timer function from the function list in Appendix A...

Page 8: ...OFF OFF ON ON 11 ON OFF ON ON 4 OFF ON OFF OFF 12 ON ON OFF OFF 5 OFF ON OFF ON 13 ON ON OFF ON 6 OFF ON ON OFF 14 ON ON ON OFF 7 OFF ON ON ON 15 ON ON ON ON Addr Controller address used with the RS...

Page 9: ...alue which will display when a 4mA signal is applied to the controller For example for a 4 20mA unit to display from 50 to 150 set LoCA to 50 e Press and hold the RETURN key for at least 5 seconds and...

Page 10: ...will extinguish The new Tuning values will now be stored in nonvolatile memory Adjustments can be made manually if desired in programming level 2 e To abort an Auto Tune process simply press and hold...

Page 11: ...s outputs to maintain the desired limit programmed by the user A setting of zero defeats the Ramp to Setpoint function 11 2 Soak Timer Function for use with Alarm 1 only The Alarm 1 Soak Timer allows...

Page 12: ...nce and proper packaging to prevent damage in transit This warranty does not apply to defects resulting from action of the user such as misuse improper wiring operation outside of specification improp...

Page 13: ...e Same as the Process Low Alarm but no relay action takes place until the process PV reaches the setpoint for a second time Standby sequence is also known as Startup Inhibit and is useful for avoiding...

Page 14: ...nding upon the alarm type where no relay action can occur to eliminate relay chatter Act Action This is control output action Set to 1 for heating unit Set to 1 for o F dp decimal point Set to 0 for n...

Page 15: ...which the controller s secondary cooling output is permitted to throttle between 0 and 100 Outside this region the controller s secondary output is either 0 above the band or 100 below the band Figure...

Reviews: