INPUT INSTANCE DATA MAP
The 4 integers of the input instance are for future use and have no operation at this time.
OUTPUT INSTANCE DATA MAP
The following table describes the output instance of the Marquee and gives a description on each
attribute of the instance.
Table 4—Output Instance Data Map
Offset
Operation
Description
0
Enable
Enable Marquee Communications must always be a
value of 1
1
Message Register 1
Message number to display or if the marquee is in BIT
MESSAGE CALL-UP then controls messages 1-16.
2
Message Register 2
Message number to display or if the marquee is in BIT
MESSAGE CALL-UP then controls messages 17-32.
3
Message Register 3
Message number to display or if the marquee is in BIT
MESSAGE CALL-UP then controls messages 33-48.
4
Message Register 4
Message number to display or if the marquee is in BIT
MESSAGE CALL-UP then controls messages 49-64.
5
Variable Data Register 0
For embedding data into message as @0
6
Variable Data Register 1
For embedding data into message as @1
7
Variable Data Register 2
For embedding data into message as @2
8
Variable Data Register 3
For embedding data into message as @3
9
Variable Data Register 4
For embedding data into message as @4
10
Variable Data Register 5
For embedding data into message as @5
11
Variable Data Register 6
For embedding data into message as @6
12
Variable Data Register 7
For embedding data into message as @7
13
Variable Data Register 8
For embedding data into message as @8
15
Variable Data Register 9
For embedding data into message as @9
16-31
Future Use