2 Standards and Approvals
The products have been designed for use in an industrial environment in compliance with the 2014/30/
EU EMC Directive.
The products have been designed in compliance with:
EN 61000-6-4
EN 55011 Class A
EN 61000-6-2
EN 61000-4-2
EN
61000-4-3
EN
61000-4-4
EN
61000-4-5
EN
61000-4-6
EN
61000-4-8
EN60945
EN 60079-0
EN 60079-15
EN 60079-31
IECEx
IECEx: IECEx ULD 16.0007X
IEC 60079-0, Ed.6
Ex nA IIC T4 Gc -20<Tamb<+60°C (0≤Tamb≤+50°C for PLIO03)
IEC 60079-15, Ed.4
Ex tc IIIC T105°C Dc
IEC 60079-31, Ed.2
ATEX
DEMKO 16 ATEX 1683X
EN 60079-0: 2012+A11:2013 II 3G Ex nA IIC T4 Gc -20<Tamb<+60°C (0≤Tamb≤+50°C for PLIO03)
EN 60079-15: 2010
II 3D Ex tc IIIC T105°C Dc
EN 60079-31: 2014
The installation of these devices into the residential, commercial and light-industrial environments is allo-
wed only in the case that special in measures are taken in order to ensure conformity to EN 61000-6-3.
The products are in compliance with the Restrictions on Certain Hazardous Substances (RoHS) Directive
2002/95/EC
In compliance with the above regulations the products are CE marked.
Special instruction for use
- The equipment shall only be used in an area of not more than pollution degree 2, as defined in IEC/
EN 60664-1.
- The equipment shall be installed in an enclosure that provides a degree of protection not less than IP
54 in accordance with IEC/EN 60079-15.
- Transient protection shall be provided that is set at a level not exceeding 140 % of the peak rated vol-
tage value at the supply terminals to the equipment.
- Care shall be taken not to allow layers of dust to form on the graphic panel in a way that might cause
the accumulation of static charges.