52
• Menu sequence and structure
3110086 EHC20 UK 110515
6.2.3.7 0-10V on
The pump needs this voltage in order to switch on.
Setting range: (Solar:) 0.0 to 5.0 V / default: 1.0 V - (Heating:) 5.0 to 10.0 V / default: 9.0 V
6.2.3.8 0-10V max
With this value, you can specify the maximum voltage level for the highest speed of an energy-saving pump which will
be used during purging or manual operation for example.
Setting range: (Solar:) 5.0 to 10.0 V / default: 10.0 V - (Heating:) 0.0 to 5.0 V / default: 0.0 V
6.2.3.9 Rotational speed when ”On”
In this menu, you can change the basis for calculating the rotational speed shown. If, for example, 30% is specified
here, 30% rotational speed will be shown when applying the frequency/voltage under ”PWM On” / ”0-10 V On”. If the
frequency/voltage for ”PWM Max” / ”0-10 V Max” is applied, 100% rotational speed will be shown. Intermediate values
will be calculated accordingly.
Setting range: 10 to 90% / default: 30%
This function does not influence control functions. It merely influences the display on the
status screen.
6.2.3.10 Show signal
Shows the pump signal set in a graphical and text overview.
6.2.3a Example pump settings
Max rpm
Rotational speed
5-20% Stop
0-5% Cable Breakage detection
25% Start
25-90% Limits of regulation
Min rpm
PWM-Signal (%)
0
20% 25%
50%
100%
Stop
Start
5%
PWM out 5% - 20%
PWM in >=25%
PWM max <=90%
90%