4. 

Pressure regulation of exodraft chimney fans

4.1 

 Application

Field of application

•  EBC24 can also be used for boiler systems with modulating burners.

•  The automation is designed for both solid fuel boilers, atmospheric gas boilers, and boilers with oil and 

gas blow torches.

•  EBC24 can control a chimney fan directly or indirectly via a frequency converter.

4.2 

Functioning

General function

•  The automation monitors the draft in the chimney, disabling the burner in case of malfunction (the alarm 

diode on the EBC24 turns on).

•  When the boiler thermostat demands heat, the chimney fan will start at max. voltage.

•  When the EBC24 registers sufficient chimney draft, the burner is released. 

•  The EBC24 maintains the set pressure by regulating the voltage. The pressure is shown in the display.

•  In the event of insufficient venting, the burner will initially be disconnected after 15 seconds. Insufficient 

venting is less than 64% of the set value, corresponding to less than 80% of flow.

•  When the boiler turns off, the chimney fan stops as well. It is, however, possible to set a post-purge period 

for the chimney fan (see page 23). Alternatively, the control system can be connected in a way that keeps 

the chimney fan running continuously (see page 21). 

Light-emitting diodes and output signals

All inputs and outputs are connected to a light-emitting diode for monitoring and servicing of the system (see section 

2.9.1 Light-emitting diodes and terminal board, page 17)

EBC24 has 0-10V output signals for control of multiple chimney fans via frequency converters or motor power relays.

4.3 

Electrical connection

This work must be performed by a qualified electrician in accordance with locally applicable rules and 

legislation.

Installation of the supply cable must comply with applicable legislation and regulations.
The grounding terminal ( 

  ) must always be connected.

When connecting a pressure transducer (XTP) and frequency converter, shielded cable must be used. 

Isolation switch

exodraft a/s stresses that according to EU’s Machinery Directive, an isolation switch must be 

incorporated into the fixed installation. The isolation switch is not supplied by exodraft, but is available 

as an accessory.

4.4 

Wiring examples

As a constant pressure regulator for exodraft chimney fans, the EBC24 can be connected to a range of different signals. 

The following pages are wiring examples and illustrate the following:

•  4.4.1 One boiler, page 20

•  4.4.2 One boiler med potential free contact, page 21

•  4.4.3 One boiler and extra monitoring with PDS, page 21

•  4.4.4 One boiler connected to frequency converter, page 23

•  4.4.5 Two boilers with continuous operation of chimney fan, page 24

exodraft recommends contacting the boiler manufacturer for correct connection to the boiler 

automation.

3120073-UK EBC24

Pressure control • 

19

Summary of Contents for EBC24 Series

Page 1: ...Fitting installation and operating instructions EBC24 UK Read and save these instructions...

Page 2: ...ting diodes and terminal board 17 3 2 2 Switch between the basic functions of pressure control and supply air 18 4 Pressure regulation of exodraft chimney fans 19 4 1 Application 19 4 2 Functioning 19...

Page 3: ...al injury or material damage TO REDUCE THE RISK OF FIRE ELECTRICAL SHOCK OR INJURY OBSERVE THE FOLLOWING Use this unit in the manner indicated by the manufacturer If you have questions contact the sup...

Page 4: ...alarm relay Max 230 VAC 4A AC1 24 VDC 2A DC1 Boiler inputs 10 48 VDC 10 230 VAC VFD Relay Max 230 VAC 2A AC1 24VDC 2A DC1 Output TRIAC VAC 10 230 Dimensions AxBxC 175 x 175 x 100 mm Weight kg 1 5 IP...

Page 5: ...t setting EBC24 ensures and monitors consistent pressure in the chimney EBC24 can also be used for boiler systems with modulating burners The automation monitors the draft in the chimney disabling the...

Page 6: ...r EBC24EU02 3200813 Measures pressure in the chimney EBC24EU02 E 2 m Silicone hose 2000335 Supplies the pressure transducer XTP with reference pressure from the measuring probe or from outdoors Instru...

Page 7: ...rom wind and weather rain snow etc Supply air fan Install the control and the pressure transducer XTP in the boiler room Connect the hose for measuring reference pressure outdoor atmospheric pressure...

Page 8: ...r entry If the pressure transducer is positioned where insects have access to the free end installing a sinter filter is recommended 2 3 Layout of the user interface 2 3 1 Panel Pos Del Funktion A USB...

Page 9: ...appliance boiler 1 thermostat optocoupler 10 230V AC DC 29 24 VDC power supply Max 100 mA 13 Voltage input from appliance boiler 1 thermostat optocoupler 10 230V AC DC 30 PDS NC normally closed Prove...

Page 10: ...ucer in an airtight enclosure It uses the boiler room pressure atmospheric pressure as reference pressure The control can be installed directly on the wall or somewhere similar Take off the lid The in...

Page 11: ...four buttons with the following functions Tast Funktion Activate the service menu press and hold for 5 seconds and enter code 3142 Edit and save settings Go to menu item and adjust value Return to ope...

Page 12: ...mode 1 5 Sensor Range min and max 1 6 Properties See page 15 2 9 Service menu overview Menu 2 2 1 Error Alarm type 2 2 Error log Alarm log covering 19 readings 2 3 Reset Automatic or manual Menu 3 3 1...

Page 13: ...rt the system EBC24 displays the actual negative pressure in this example 55 Pa 2 Press and hold for 5 seconds to get into the service menu Enter code 3142 Select menu 1 3 Select menu 1 1 4 Set requir...

Page 14: ...is exam ple 55 Pa 2 Press and hold for 5 seconds to get into the service menu Enter code 3142 Select menu 1 w 3 Regulation 1 Select menu 1 2 Pre purge Select menu 1 3 Post purge 4 Select either 1 3 1...

Page 15: ...set point SET EXHAUST Adjustment of exhaust setpoint 2 95 af sensor 17 12 Operation mode EXHAUST MODE Continuous or intermittent operation In inter mittent mode the exhaust fan runs only if one or mo...

Page 16: ...lers to be activated even though no sufficient draft is present 0 250 s off Off 333 Draft Input Delay DRAFT INPUT DELAY The delay before the control goes into Fraft Alarm 0 20 s 0 s 34 Factory reset F...

Page 17: ...C V AC green the input is active 14 og 15 BURNER 1 OUT 250 V AC 4A AC3 green the relay is closed 16 og 17 BOILER 2 IN 18 til 230 V DC V AC green light the input is active 18 og 19 BURNER 2 OUT 250 V A...

Page 18: ...ic function Step Action Display shows 1 Press and hold for 5 seconds 2 Enter code 3142 Use arrows to select followed by 3 Select menu 1 Regulation Select menu 1 6 Properties 4 Select menu 1 6 9 applic...

Page 19: ...ts are connected to a light emitting diode for monitoring and servicing of the system see section 2 9 1 Light emitting diodes and terminal board page 17 EBC24 has 0 10V output signals for control of m...

Page 20: ...signal 18 230 V AC DC to EBC24 to start stop the chimney fan Connect the supply to terminals 1 3 Connecting the boiler Connect the burner start signal L to terminal 12 Connect the neutral wire to ter...

Page 21: ...ample shows how to connect a potential free contact to the EBC24 to start stop the fan Connect the supply voltage to terminals 1 3 Connection to the boiler Connect the potential free contact to termin...

Page 22: ...DS supplies extra monitoring Connecting PDS Remove the factory installed wiring between terminals 30 and 32 Connect PDS to terminals 30 31 and 32 Connect the supply to terminals 1 3 Connecting the boi...

Page 23: ...Frequency converter Connect terminals 7 8 to the start stop input on the frequency converter Connect terminals 21 22 to the frequency converter input for external speed regulation If needed connect t...

Page 24: ...onnect the EBC24 if you require continuous operation of the chimney fan Connect the supply to terminals 1 3 Loop terminals 13 17 28 Loop terminals 12 16 29 Connecting the boiler example with two boile...

Page 25: ...function ensures that if the pressure in the boiler room is insufficient the EBC22 will shut down the boilers the EBC24 will shut down the boilers should the pressure in the boiler room become insuffi...

Page 26: ...to the start stop input on the frequency converter Connect terminals 20 21 input for external speed regulation If needed connect terminals 30 and 32 to the alarm output of the frequency converter Conn...

Page 27: ...reenstemming met de voorschriften uit de hieronder genoemde normen en standaards som omfattas av denna deklaration verensst mmer med f ljande standarder jota t m selvitys koskee on seuraavien standard...

Page 28: ...draft se www exodraft se NO exodraft a s Storgaten 88 NO 3060 Svelvik Tel 47 3329 7062 info exodraft no www exodraft no UK exodraft Ltd 10 Crestway Tarleton GB Preston PR4 6BE Tel 44 0 1494 465 166 Fa...

Reviews: