6.3 Water heating system
Water heating coil
HCW
Weight
Weight without fluid
9.5 kg
Water content
2.4 l
Dimensions
Face area (h x b)
475 x 760 mm
Data
Test pressure
3000 kPa
Max. operating pressure
1000 kPa
Number of rows of pipes
qty. 2
Number of circuits
qty. 5
Pipe connection
DN20 (¾")
Fin spacing
2.1 mm
Permissible media temperature
5..0.95
℃
Recommendation
A precise calculation of the heating coil is recommended, to be carried
out with calculation program EXselect, available on www.exhausto.dk.
6.3.1 MVM motor valve
Valve
K
VS
1.0 - 4.0
K
VS
6.3
Test pressure
1600 kPa
1600 kPa
Max. differential pressure
100 kPa
200 kPa
Permissible media temperature
5°C - 110°C
5°C - 110°C
The valve will remain permanently
open if the differential pressure
is greater than 100
kPa
is greater than 200
kPa
Motor
K
VS
1.0 - 4.0
K
VS
6.3
Permissible ambient temperature
-30
℃
- 50
℃
-30
℃
- 50
℃
Ingress protection, in accordance with
IEC
IP40
IP40
Time taken to open/close
34 s
30 s
Power supply (50/60 Hz, AC/DC)
24 VAC ±20%
24 VDC ±20%
24 VAC ±20%
24 VDC ±20%
Regulation
0–10 VDC
0–10 VDC
3005706-2017-06-08
Technical data
30/36