Step
Action
2
Carefully remove the bypass (do not wrench it out)
3
Make sure the Tice sensor/fitting is free of the coun-
terflow heat exchanger before extracting it.
4
Remove the counterflow heat exchanger all the way.
Note the weight of the heat exchanger, see techni-
cal data – min. two people when lifting.
5
Clean the counterflow heat exchanger by flushing with hot water or by pressure hosing.
Max. water temperature 90°C.
6
Replace the counterflow heat exchanger and then the
bypass.
Check that the Tice sensor is correctly positioned be-
tween the heat exchanger fins, as the sensor will not
measure correctly otherwise.
7
Re-insert the plug for the bypass motor.