3004343_2018_01_12.fm
26/36
How to connect
TIMERBUTTON/
TIMERBUTTONEU
to EXact2
• Connect TIMERBUTTON/TIMERBUTTONEU according to the following diagram
* Not supplied by EXHAUSTO
Start/stop of VEX
• Remove the jumper between terminals 24 and 25 on the EXact2 PCB.
• Mount a suitable 2-conductor cable between TIMERBUTTON/
TIMERBUTTONEU and External start (terminals 24 and 25)
• Note that TIMERBUTTON/TIMERBUTTONEU must have a separate 24V AC/
DC voltage supply.