cLAN3524-XF / cLAN3524-MQ
Hardware features
Ethernet port: RJ45 10/100 Mbit
Serial ports: 2 (Both are RS232 and RS485)
Digital Inputs : 16 voltage activated (8 of them can count pulses of up to 1 Khz)
Analog Inputs: 8 configurable as 0-1V / 0-10V / 4-20mA
Digital Outputs: 8 open collector type
Power supply requirements: 10 to 30 Vdc
Dimensions: 85 x 60 x 105 mm (Height x Width x Length)
Operation Temperature: -15°C a +65ºC
Data Acquisition
Physical inputs/outputs
Modbus inputs/outputs (embedded Modbus master)
Embedded Modbus slave
Other protocols using script programming
Operating modes:
XF model : Monitoring by WEB page / Database (Ethernet datalogger)
MQ model : MQTT client
Monitoring from SCADA
Remote access to serial port
Telemetry Controller
Local I/O control (using the script programming feature)
Direct connection with SCADA using its Modbus RTU and Modbus TCP slaves
Server link :
Ethernet (Local network or using the Internet)
Satellital (with external satellite modem, XF model only)
Wiring
Wiring – Power supply
Wiring – RS232 port – RS485 port
The
RS232
port is of the 5-wire DTE type (TX, RX, RTS, CTS, GND) and has a terminal board for its
connections.
The
RS485
port is of the 2-wire type (TR+ and TR-) and has a terminal board for its connections.
There's no need to configure whether you are going to use the port RS232 or RS485. Just connect the
wires to the corresponding terminals.
cLAN-MQ User Manual
cLAN3524-MQ
69 / 73
Summary of Contents for cLAN-MQ Series
Page 14: ...2020 11 19 cLAN MQ User Manual cLAN Configurator 13 73 ...
Page 22: ...Analog inputs cLAN MQ User Manual Physical Inputs Outputs 21 73 ...
Page 30: ...2020 09 28 cLAN MQ User Manual Features of power supply and inputs outputs 29 73 ...
Page 59: ...2020 11 20 cLAN MQ User Manual Scripts Publish Subscribe 58 73 ...
Page 66: ...2020 09 28 cLAN MQ User Manual cLAN2205 MQ 65 73 ...
Page 69: ...2020 09 28 cLAN MQ User Manual cLAN3404 MQ 68 73 ...