cLAN-2205 in XF and MQ versions
Parameter
Maximum
Units
Withstand voltage
50
Vdc
Current
200
mA
Digital outputs to actuate a Relay
When the digital output is used to actuate a relay coil a protection diode must be added to the connection
to avoid damage to the output of the equipment. This must be connected in reverse, that is the anode to
the output terminal of the equipment and the cathode to the positive terminal feeding the relay. The relay
must be fed using an external power supply, sharing the GND terminal with the power supply of the
equipment, or if necessary the same power supply feeding the cLAN can be used.
The following graph shows how to connect a relay to a digital output of the equipment.
Analog Inputs
cLAN-3424 Analog inputs refer to the GND Terminal of the equipment, consequently, the power supply
used to feed the sensor must share the GND terminal with the equipment.
cLAN-3524 in XF and MQ versions - Voltage inputs (0-10V / 0-1V)
Parameter
Value
Units
cLAN-MQ User Manual
Features of power supply and inputs/outputs
26 / 73