Parameter
Value
Units
Full scale
10 / 1
Vdc
Resolution
1 / 0.1
mV
Input impedance
>600
KΩ
Analog inputs are diferential (two terminals per input)
Sensors with voltage output (0-10V) can be connected to the device as shown in the following
figure.
cLAN-3404 in XF and MQ versions - Current inputs (4-20mA)
Parameter
Value
Units
Full scale
20
mA
Resolution
10 / 1
uA
Shunt resistance
62
Ω
Analog inputs are diferential (two terminals per input)
In this case, sensors with current loop output (4-20mA) can be connected to the device as
shown in the following figure.
cLAN-MQ User Manual
Features of power supply and inputs/outputs