7.
While the Water Softener/Filter brine tank is filling, load two
20kg bags of Water Softener/Filter salt.
WATER SOFTENER/FILTER PROGRAMMING SETTINGS
Step
I
:
Press next and up simultaneously for 3 seconds
.
Step
II
:
Set hardness in grains per gallon using the up
and down
buttons. The default is 15 with a valve range of 1 to 150
in 1 grain increments. The display will show NA if filter is
selected. Add 5 gains of hardness for every one part of
iron, then press next to go to Step
III.
Step
III:
Day override when gallon is set to off sets the number of
days between regenerations when gallon capacity is set
to auto or to a number sets the maximum number of days
between regenerations. If valve set to off regeneration
initiation is based solely on gallons used. If valve is set
as a number allowable range 1 to 28 days. A
regeneration initiation will be called for on that day even if
sufficient number of gallons were not used to call for
regeneration. Set day override using down or up buttons.
Step
IV
:
Press next regeneration time (hour). Set the hour of the
day for regeneration using down or up buttons. AM/PM
toggles after 12. The default time is 2:00AM.
To initiate a manual regeneration immediately, press and hold the
regen button for three seconds. The system will begin to regenerate
immediately. The Water Softener/Filter control valve may be stepped
through the various regeneration cycles pressing the regen button.