E-80-136KTL User Manual
Copyright ©EVOLVE ENERGY GROUP CO.,LTD
- 68 -
9.2.
Output Parameter (AC)
Parameter
E-
75KTL
E-
80KTL
E-
100KTL
E-
110KTL
E-
100KTL-
HV
E-
125KTL-
HV
E-
136KTL-
HV
Rated Power
75KW
80KW
100KW
110KW
100KW
125KW
136KW
Max AC
power
75KVA
88KVA
110KVA
121KVA
110KVA
137KVA
150KVA
Rated output
current
108A
116A
144A
160A
128A
144A
145A
Max output
current
120A
128A
160A
175A
128A
160A
160A
Nominal grid
voltage
3/N/PE,230V/400Vac
,
220V/380Vac
3/PE,500Vac
3/PE,54
0Vac
Grid voltage
range
310Vac-480Vac
400Vac-575Vac
432~62
1
Vac
Nominal
frequency
50Hz/60Hz
Grid
frequency
range
45Hz-55Hz/54Hz-66Hz (According to local standard)
THDi
<3%
Power Factor
1 default ( adj/-0.8)