Use multimeter to confirm that three lines and PE line are connected correctly.
DC PV connection.
Use multimeter to confirm that positive pole and negative pole of PV strings, and
the Voc of each string is lower than the inverter max DC input.
6.2.
Start Inverter
Step 1:
Turn ON the DC switch.
Step 2:
Turn ON the AC circuit breaker.
When the DC power generated by the solar array is enough, the E-
75~136KTLinverter will start automatically. Screen showing” normal
”
indicates
correct operation.
NOTE 1:
Choose the correct country code. (refer to section 7.3 of this manual)
NOTE 2:
Different distribution network operators in different countries have different
requirements regarding grid connections of PV grid connected inverters.
Therefore, it is very important to make sure that you have selected the correct
country code according to requirements of local authority. Please consult qualified
electrical engineer or personnel from electrical safety authorities about this.
EVOLVE ENERGY GROUP CO.,LTD is not responsible for any consequences
arising out of incorrect country code selection.
If the inverter indicates any fault, please refer to Section 8.1 of this manual
——
trouble shooting for help.