36
INSTALL
SENSOR CALIBRATION
INSTALLER
ZONES MANAGER
SYSTEM RESET
ADD ZONE
MODIFY ZONE
DELETE ZONE
INSTALL
INSTALLER
-
Select the desired heating zone and then choose from
among the options with the
“up”
and
“down”
keys,
confirming the selection:
MAIN
INSTALLER
INSTALL
-
TYPE OF ACTUATION
Set the parameter in question to ITRF05/AKM (default
value)
-
TYPE OF HEAT REQUEST
This parameter allows you to specify the type of heat
request, it is possible to choose from among the following
options:
THERMOSTAT
(factory setting): the heat request is
generated with an ON/OFF thermostat
REC10 MASTER:
the heat request is generated by the
REC10 MASTER; in this case the REC10 assumes the
function of an HIU (Human Machine Interface)
-
TYPE OF ZONE
This parameter allows you to specify the type of zone
to be heated, it is possible to choose from among the
following options:
HIGH TEMPERATURE (factory setting):
LOW TEMPERATURE
-
MIN SET HEAT
This parameter allows you to specify the minimum heating
setpoint that is possible (range 20°C - 80.5°C, default
40°C for high temperature systems - range 20°C - 45°C,
default 20°C for low temperature systems)
-
MAX SET HEAT
This parameter allows you to specify the maximum
heating setpoint that is possible (range 20°C - 80.5°C,
default 80.5°C for high temperature systems - range 20°C
- 45°C, default 45°C for low temperature systems)
-
CHANGING NAME
This parameter allows you to attribute a specific name to
the heating zone
-
POR (embedded clock function)
This parameter enables or disables the embedded clock.
Embedded clock disabled (default) = 0
Central heating is controlled (ON & OFF) by the room
thermostat connection (TA).
Embedded clock enabled = 1
Central heating ON/OFF times are controlled according to
the (default) heating programme, whilst room temperature
is controlled via the room thermostat (TA). Ensure that the
operating mode (‘STATE’ menu) is set to AUTO.
6.2.3 EMBEDDED CLOCK HEATING SCHEDULE
When the embedded clock is enabled (POR=1 - see above),
a default heating schedule is used to manage the ON/OFF
timings for each day of the week (operating mode = AUTO).
if necessary, the default heating schedule can be changed
according to the User’s needs. Refer to section 2.10 for
detailed instruction/guidance on how to access and change
the default heating schedule.
18/05/2013
12:17
30
°C
.3
1.3 bar
MENU
INFO
SET
FRI
HOT WATER TEMPERATURE
STATE
PLANT
MON
SETTINGS
MENU
SELECT OPTION
TIME SCHEDULE
MON
18/11/2013
12:17
MAIN
SELECT THE ZONE
SCHEDULE
07:30
11:30
18:00
08:30
13:30
22:30
SELECT
A DAY
START
MAIN
THURSDAY
END
ZONE SCHEDULE
6.2.4 SETTING THE THERMOREGULATION
Thermoregulation (weather compensation) controlled by the
appliance, can only be enabled if an external sensor has been
installed and connected to the D-sub interface (SE terminals
11 & 12).
When the presence of an external sensor is detected, the
appliance immediately enables the thermoregulation function
and calculates a required outlet (flow) temperature that is
based on the external temperature and the chosen climatic
curve.
The temperature measured by the outdoor temperature
sensor is displayed on the initial page in the top right,
alternating with the display of the time.
When thermoregulation is enabled (outdoor temperature
sensor present), the algorithm for automatically calculating
the outlet setpoint depends on the type of heat request.