4.2
Installation Site
Select a suitable location for the unit, where the unit will not be subject to any damage.
a) The unit must be mounted on a flat and level foundation capable of supporting the entire operating
weight of the equipment.
b) The location must not contain corrosive-chemical storage or connect to any space that contains corrosive-
chemical storage.
c) The location must not include a natatorium or spa room, or any space where the exterior of the unit
would be exposed to chloramines outgassing from a pool.
d) Ensure that water cannot collect under the unit, it is recommended that units are installed on plinths
100mm above finished floor level. This also aids condensate drainage.
e) Please allow adequate clearance to service panels on the unit; recommended 800mm minimum.
f) Ensure loose debris such as leaves, grass cuttings, etc will not block air inlet grilles.
g) Consider protection from extreme weather conditions if installed externally.
h) Inadequate working spaces may compromise workplace safety. Inadequate working spaces may preclude
proper maintenance.