Alarm and Troubleshooting
The alarm messages detected by the dehumidifier are displayed as below:
ALARM MESSAGE
CAUSE
SOLUTION
DEHUMIDIFIER
1# Tube temperature
sensor failure
Sensor problem
Change a new one
Only the faulty
system stops
Sensor wire is loose
Fasten the sensor wire
1# Compressor low
pressure protection
Fan motor problem
Check fan motor
Only the faulty
system stops
Obstruction is return duct system Remove duct obstruction
Expansion valve problem
Replace expansion valve
1# Compressor high
pressure protection
A/C condenser power off
Restore power to A/C
Only the faulty
system stops
A/C condenser fan gets blocked
Remove blockage
Excessive refrigerant charge
Remove charge to proper amount
A/C 4-way valve is not opening
Repair A/C 4-way valve
1# Compressor Overload
protection
Low refrigerant charge
Properly charge refrigerant
Stops
Fan valve motor problem
Check fan motor
1# Compressor Discharge
temperature over the
limit
Refrigeration system problem
Check the whole refrigeration system
The faulty system
will stop after 3
times
1# Compressor discharge
temperature sensor
Sensor problem
Change a new one
Only the faulty
system stops
Sensor wire is loose
Fasten the sensor wire
2# Tube temperature
sensor failure
Sensor problem
Change a new one
Only the faulty
system stops
Sensor wire is loose
Fasten the sensor wire
2# Compressor low
pressure protection
Fan motor problem
Check fan motor
Only the faulty
system stops
Obstruction is return duct system Remove duct obstruction
Expansion valve problem
Replace expansion valve
2# Compressor high
pressure protection
A/C condenser power off
Restore power to A/C
Only the faulty
system stops
A/C condenser fan gets blocked
Remove blockage
Excessive refrigerant charge
Remove charge to proper amount
A/C 4-way valve is not opening
Repair A/C 4-way valve
2# compressor overload
protection
Low refrigerant change
Properly charge refrigerant
Stops
Fan valve motor problem
Check fan motor
2# compressor discharge
temperature over the
limit
Refrigeration system problem
Check the whole refrigeration system
The faulty system
will stop after 3
times
2# Compressor discharge
temperature sensor
failure
Sensor problem
Change a new one
Only the faulty
system stops
Sensor wire is loose
Fasten the sensor wire
3# Tube temperature
sensor failure
Sensor problem
Change a new one
Only the faulty
system stops
Sensor wire is loose
Fasten the sensor wire
3# Compressor low
pressure protection
Fan motor problem
Check fan motor
Only the faulty
system stops
Obstruction in return duct
system
Remove dust obstruction
Expansion valve problem
Replace expansion valve
3# Compressor high
pressure protection
A/C condenser power off
Restore power to A/C condenser
Only the faulty
system stops
A/C condenser fan gets blocked
Remove blockage
Excessive refrigerant charge
Remove charge to proper
A/C 4-way valve is not opening
Repair A/C 4-way valve
3# Compressor overload
protection
Low refrigerant charge
Properly charge refrigerant
Stops
Fan valve motor problem
Check fan motor
3# Compressor discharge
temperature over the
limit
Refrigeration system problem
Check the whole refrigeration system
The faulty system
will stop after 3
times