evoheat Solace Universal C-1200 Installation & Operation Manual Download Page 13

P a g e

 | 

13 

 

 

4.7

 

Pipe Installation 

Installation of the outdoor air-cooled condenser should only be done by a qualified refrigeration mechanic 

familiar with this type of work. Many service problems can be avoided by taking adequate precautions to 

provide an internally clean and dry system and by using procedures and materials that conform to 

established procedural standards. 

1.

 

Materials 

 

Use clean, dehydrated, refrigeration-grade copper tubing for all refrigerant lines. Hard drawn tubing should be 

used where no appreciable amount of bending around pipes or obstructions is necessary. If soft copper tubing 

must be used, care should be taken to avoid sharp bends which may cause restrictions and excessive refrigerant 

pressure drops. 

 

Use long radius elbows wherever possible with one exception - short radius elbows should be used for any traps 

in the hot gas riser. 

 

Braze all copper to copper joints with a phosphorus-copper alloy material such as Silfos 5 or equivalent. Do not 

use soft solder. 

 

During brazing operations flow an inert gas, such as nitrogen, through the lines to prevent internal oxidation 

scaling and contamination. 

 

Support refrigeration lines at intervals with suitable hangers, brackets or clamps. 

 

Pack glass fiber insulation and a sealing material around refrigerant lines, where they penetrate a wall, to 

reduce vibration and to retain some flexibility. 

 

The liquid line and discharge line should not be in contact with one another. If the installing contractor must tie 

these lines together because of an installation requirement, the contractor must insulate them from each other 

to prevent heat transfer. Because the discharge line is hot during system operation, precautions should be 

taken to avoid personnel injury. 

2.

 

Sizing 

 

The lines must be sized and routed so that oil is carried through the system. Using smaller lines than 

recommended will give excessive pressure drops, resulting in reduced capacity and increased power 

consumption. Oversized lines could result in an oil flow problem within the system and possible compressor 

damage. 

 

Excessive pressure drops in the liquid line may cause flashing of the refrigerant and a loss of a liquid seal at the 

expansion valve inlet. A reduction in capacity may then occur because the presence of gaseous refrigerant will 

partially block the expansion valve. Using hot gas and liquid line sizes recommended in the Air Cooled 

Condenser section for these units and the proper system refrigerant charge will prevent this problem. 

 

Discharge lines should be designed to prevent condensed refrigerant and oil from draining back to the 

compressor during OFF cycles. 

 

NOTE 

The size of the Copper 

Pipe: 2pcs of 25mm, 2pcs 

of 19mm 

Summary of Contents for Solace Universal C-1200

Page 1: ...P a g e 1...

Page 2: ...14 6 Start up Check List 14 6 1 Pre Start Checklist 14 6 2 Start Up 15 7 Operation 16 7 1 How to Control 16 7 2 Run Mode Menu 17 7 3 Alarms Menu 20 7 4 Sensors Off Set Menu 20 7 5 Run state Menu 21 7...

Page 3: ...ion is satisfied SPACE HEATING When the compressor is running space heating will continue until the space temperature reaches the set point The controller will activate the auxiliary space heating sys...

Page 4: ...or This hot gas refrigerant then travels either through an air reheat coil the pool water condenser or to an optional auxiliary air conditioning condenser which may be either air or water cooled If ai...

Page 5: ...erated in an abnormal condition it may cause a fire or hazards Apply Grounding Do not connect a grounding wire to a gas pipe water pipe lightning rod or ground wire of a telephone If a grounding is in...

Page 6: ...ric shock water leakage etc Ensure that you consult your dealer Do not apply an insecticide or flammable spray It may cause a fire or deformation of the cabinet Do not clean the unit with water Water...

Page 7: ...P a g e 7 4 Installation 4 1 Installation Diagram...

Page 8: ...ace where the exterior of the unit would be exposed to chloramines outgassing from a pool d Ensure that water cannot collect under the unit it is recommended that units are installed on plinths 100mm...

Page 9: ...P a g e 9 4 3 Ducts Installation...

Page 10: ...g see data sheet H R C Fuses are recommended An isolator must be fitted within clear view of the machine and not more than 2 meters away The isolator must have a minimum of 3mm air gap when in the off...

Page 11: ...n the boiler water flow and return pipes local to the dehumidification unit Refer to the boiler manufacturer s instructions before designing the pipework system IMPORTANT GENERAL CONDITIONS 1 Do not r...

Page 12: ...taken to see that ample room is left for maintenance work through access doors and panels Overhead obstructions are not permitted When the unit is in an area where it is enclosed by three walls the un...

Page 13: ...and a sealing material around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility The liquid line and discharge line should not be in contact with one anot...

Page 14: ...p Check List 6 1Pre Start Checklist Before starting the unit be sure that the following items have been completed Ensure there is enough space to install the unit See Installation for installation rec...

Page 15: ...3 Disconnect power from the dehumidifier unit Re tension the blower belt Turn on the pool water supply to the unit Use valves in the water line to set the flow rate to the range called out on the unit...

Page 16: ...rmance data of Air Cooling 10 If the unit is equipped with an auxiliary air conditioning condenser change the water temperature set point lower higher than current air temperature This should cause th...

Page 17: ...ification and water heating dehumidification and air cooling The above screen contains basic information of the status and target set point status displays Space Temp Room space temperature in Space H...

Page 18: ...ns basic information of the status and the selective running mode There are three options to choose Manual Humidity Off On Ventilation Only Off On Manual Fresh Air Off On There are three different run...

Page 19: ...idDiff The humidity difference of room space relative humidity in PoolTempDiff The temperature difference of pool water temperature in AuxAirHeatDif The temperature difference for auxiliary air space...

Page 20: ...ing by an experienced HVAC technician The dehumidifier may stop when the fault occurs Press the reset button after the fault has been eliminated to go back to normal operation 7 4 Sensors Off Set Menu...

Page 21: ...5 Run state Menu The RUNSTATE screen contains the technical information of the status the dehumidifier 7 6 Curves Menu The CURVES screen is to display the value of Room Space temperature and Room Spa...

Page 22: ...er unit has numerous safety devices designed to protect the system from failures Whenever a fault condition occurs the alarm message will display on the screen The dehumidifier may stop when the fault...

Page 23: ...ct obstruction Expansion valve problem Replace expansion valve 2 Compressor high pressure protection A C condenser power off Restore power to A C Only the faulty system stops A C condenser fan gets bl...

Page 24: ...tor Only the faulty system stops Obstruction in return duct system Remove duct obstruction Expansion valve problem Replace expansion valve 4 Compressor high pressure protection A C condenser power off...

Page 25: ...P a g e 25 9 Circuit Diagram C 1200 C 1500 THREE PHASE 3 N 50Hz...

Page 26: ...P a g e 26 10Dimension and Parts 10 1 Description of Parts and Dimensions Dehumidifier Indoor Unit...

Page 27: ...P a g e 27 Air Cooled Condenser Outdoor Unit...

Page 28: ...ensate is not overflowing Check the condensate and overflow lines to ensure that neither are clogged C Check the operation of the blower motor and compressor Ensure that the compressor does not rub th...

Page 29: ...nt Type R407c Protections Type Phase Protection High Low Pressure Protection Overload Protection Water Proof PCB Compressor staged start Compressor Auto Protection Fan Motor Auto Protection Condenser...

Page 30: ...ealer s information You also need to record the model name and serial number You can find this information from your dehumidifier or ask your dealer Model number ______________________________________...

Reviews: