7.2 Error Codes 

Malfunction 

Display 

Cause 

Solution 

Bottom water temp. sensor 
failure 

P01 

1.  Check connection between the sensor to the PC board. 

 

2.  Check the resistance of the sensor, if the resistance is greater 

than 500k or less than 100 this means the sensor is broken and 
will need to be replaced. 

Top tank water temp. sensor 
failure 

P02 

Ambient temp. sensor failure 

P04 

Coil temp. sensor failure 

P05 

Suction temp. sensor failure 

P07 

Solar control temp. sensor 
failure 

P034 

High pressure protection 

E01 

1.  Check if the inlet/outlet water temp. difference is too high 
2.  Check the water flow 
3.  The target temp. setting needs to be reduced if it is too high 
4.  Check the high-pressure switch. If the switch is open when the 

connection is closed, replace it. 

Low pressure protection 

E02 

1.  Check if the system is leaking 
2.  Check the low pressure switch 
3.  Ensure the installation location allows for heat dissipation 
4.  Check the fan motor  
5.  Ensure the throttling device is not stuck 
6.  If all above are as normal, replace the PC board 

Communication failure 

E08 

1.  Check the connection between the wired controller and PC board 
2.  Replace the wire controller 
3.  Replace the PC board 

Anti-freeze protection in 
winter 

E09 

1.  Check that the high and low pressure switches are working 

normally 

2.  Check both the water tank lower temp. sensor & ambient temp. 

sensor to see if they are working normally 

3.  See if the lower temperature of the tank is lower than 10, and the 

ambient temp is lower than 0 degrees. 

 

 

 

 

 

Summary of Contents for Evo315-C

Page 1: ......

Page 2: ...ller 7 6 2 Operating Functions 8 6 2 1 Startup Shutdown 8 6 2 2 Switching Modes 8 6 2 3 Locking the Controller 8 6 2 4 Setting Checking the Target Temperature 9 6 2 5 Hydroboost Setting 9 6 2 6 Force...

Page 3: ...dvanced energy efficiency technologies and built in smart features to ensure you re provided with clean safe and economical hot water all year round Conforms to AS 3498 2009 Australia and New Zealand...

Page 4: ...year d Press at any stage to cancel 3 Press until is displayed This will activate Eco Heating Heat Pump only mode and will provide the most efficient heating 4 During periods of unusually high hot wa...

Page 5: ...you restart the unit or turn it on manually the unit will not start to run again for approximately 3 minutes This is a protection feature to safeguard the compressor The handle of the P T safety valv...

Page 6: ...eat resistant and durable Piping for the P T Valve The spec of the valve connecting thread is BSP3 4 internal thread After installation confirm that the drainpipe outlet is exposed in the air When the...

Page 7: ...nces to allow airflow to circulate through the unit it is advised to keep a minimum gap between walls fences etc of 1000mm on the air inlet outlet sides 300mm rear clearance 600mm overhead clearance W...

Page 8: ...water temperature and target temperature The electric heater always will be off INTELLIGENT MODE The unit will automatically judge the operation mode according to the ambient temperature HIGH REQUIRE...

Page 9: ...for 0 5 seconds in the running screen of the controller to turn the unit off The main display will now show OFF The unit will dim the screen and display the standby screen when the controller has not...

Page 10: ...5 Hydroboost Setting Also known as the Electric heater the Hydroboost setting allows higher levels of hot water to be produced When there are high hot water usage requirements such as guests staying t...

Page 11: ...ameter value as shown in the below table and press the key to open that value Change the value using the up down arrow keys and press the key to save changes Press to exit the menu Description Paramet...

Page 12: ...t up time A and end time B Press to save the setting and exit back to the main interface Press and hold for 2 seconds the timer display will flash When the timer display flashes choose the start up ti...

Page 13: ...sh when it is selected use the arrow keys to select your desired start day then press to save all changes and exit back to the main interface Note Format is mm dd Example The unit will start up on Sep...

Page 14: ...rs E01 EEV adjustment mode 0 1 1 0 Manual 1 Auto E02 EEV target overheat temp 20 20 5 E03 EEV initial steps 0 500 240 E04 EEV minimum steps 0 500 80 E05 Defrosting EEV steps 0 500 480 System parameter...

Page 15: ...sor shutdown ambient temp 1 30 90 65 R20 The compressor shutdown ambient temp 2 30 90 55 Timing parameters L01 Whether enable the vacation mode 0 1 0 0 Disable 1 Enable L02 The vacation mode Year 0 99...

Page 16: ...p setting needs to be reduced if it is too high 4 Check the high pressure switch If the switch is open when the connection is closed replace it Low pressure protection E02 1 Check if the system is lea...

Page 17: ...BRN BLU Y G 3G2 5mm L N L N N N N N N 1 3 2 4 5 6 7 8 01 N 4 WHT N 4V 1 2 3 4 MTS RESET 1 3 4 2 OUT1 OUT2 OUT3 OUT4 OUT5 AC N 3 4 3 4 CN5 OUT6 CN6 CN1 CN2 12V NET GND 485 A 485 B DI01 DI03 GND DI04 GN...

Page 18: ...80900421 KP cover 640 22 ABS Black Gloss 9005 Plastic Absorption 14 80708081 KP Top Cover Galvanized sheet 0 8 gray white matte 9006 15 80704839 Fan top cover Galvanized sheet 1 0 Black finish 9005 16...

Page 19: ...th the water heater 8 4 Using the Overheating Protector The overheating protector is used to turn the power off in an emergency or with power supply issues preventing the water from being heated too h...

Page 20: ...clean of the unit with a damp cloth MAJOR FIVE YEAR SERVICE It is recommended a major five 5 year service be conducted on the Evo315 C Warning Servicing of a water heater must only be carried out by...

Page 21: ...ed within the i Costs associated with delivery handling freighting or damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 933 o...

Reviews: