background image

E2660-CO-NO2

Rev 06.04.2021

Operating conditions

The device should be used both in a non-hazardous area at the atmospheric pressure
(85...110 kPa), and relative humidity in the range 15...90%, and in a basic electromagnetic
environment, where the latter is defined in EN 61326-1. Avoid strong mechanical shock and
vibrations. Avoid corrosive atmosphere and areas highly contaminated with dust, oil mist,
etc. Keep the instrument away from direct sunlight. A sudden temperature or humidity
change might affect the sensitivity of the sensor.

Installation guidelines

Before proceeding with the installation it is mandatory to read the Safety requirements
section and make sure to comply with all listed instructions. Installation standards EN
60079-29-2 and EN 45544-4 are also recommended for further instructions and related
information about the installation. During the installation of the transmitter the following
points must be considered:

Application (the instrument is intended for leakage control.)

Properties of the space under investigation (room geometry, direction, and
velocity of airflows, etc.),

Carbon monoxide has practically the same density as air. Nitrogen dioxide is 1.6
times heavier than air, but in the underground parking, it rises to the ceiling with
hot exhaustion gases, so the sensor should be located at 1.2...1.5 m from the
floor in order to detect potentially dangerous concentration more quickly.

The device should be accessible for maintenance and repair.

The aforementioned conditions above will affect the coverage area of the device. however,
the coverage area for a detector-transmitter is usually between 2.5 to 5 meters radius.

For early leakage detection install the sensor as close as possible to the potential leakage
sources (flanges, valves, pressure reducers, pumps, etc.), taking into consideration other
points listed above.

Do not locate the detector close to ventilation openings and strong air currents. Avoid the
areas without air circulation (corners, niches) as well.

For general area monitoring without definite leakage sources, the detectors should be
distributed evenly in the room.

For personal safety control, the detectors are installed in the breathing zone (at the height
of the head of people or animals). The recommended sensor position is vertical, pointing
downwards.

8

Summary of Contents for PluraSens E2660-CO-NO2

Page 1: ...PluraSens Dual Gas Detector Transmitter E2660 CO NO2 User Manual...

Page 2: ...dimensions 9 Sensor probe handling 10 Gas sensor replacement procedures 10 Electrical connections 11 Operation 13 Maintenance 13 Calibration 13 Delivery set 14 Order code for E2660 CO NO2 options 14...

Page 3: ...losive limit UEL vol in air 74 Odor Odorless Hazards Highly toxic Mild poisoning causes lightheadedness confusion headache dizziness and flu like effects Larger exposures can lead to toxicity of the C...

Page 4: ...te Irritates the skin eyes and respiratory tract Exposure to levels above 100 ppm can cause death due to asphyxiation from fluid in the lungs There are often no symptoms at the time of exposure other...

Page 5: ...scale 0 1000 0 200 0 100 Operating temperature 20 50 C 30 50 C 20 50 C Operating conditions 15 90 RH atmospheric pressure 10 non ATEX rated areas Non aggressive atmosphere Cross sensitivity Acetylene...

Page 6: ...19 EN 61000 6 2 2019 EMC Immunity EN 60079 29 1 2016 EN 60079 29 2 2015 and EN 60079 29 3 2014 Relay option Output relays 2 SPST relays closing contact 250 VAC 30 VDC 5 A max Alarm set points RE1 set...

Page 7: ...wer supply module Remote probe The version of your detector is marked on the package If the symbol is marked on the equipment consult the documentation for further information Safety requirements Misu...

Page 8: ...etry direction and velocity of airflows etc Carbon monoxide has practically the same density as air Nitrogen dioxide is 1 6 times heavier than air but in the underground parking it rises to the ceilin...

Page 9: ...E2660 CO NO2 Rev 06 04 2021 For installing the device attach the device to the wall using provided screws through the side mounting holes or key slots see mountains dimensions Mounting dimensions 9...

Page 10: ...move the old filter Place a new filter into the nut and tighten it again NOTE Never stab or press the filter near its center where the sensor is located since this may damage the sensor Do not remove...

Page 11: ...ply and of the external devices Attach the power cable to the device without turning it on Using the connection diagram below connect the analog outputs and digital interface terminals to the relevant...

Page 12: ...85 interface should not exceed 1200 m Both analog outputs can be independently changed between 4 20 mA and 0 10 V type using jumpers J1 OUT1 and J2 OUT2 By closing pins on a specific jumper the relate...

Page 13: ...ernal devices connected the power LED green on and the control LED red is constantly lit Make certain that the cable glands are properly tightened to ensure the conformity to IP65 protection class Pla...

Page 14: ...lamp for remote probe versions Order code for E2660 CO NO2 options E2660 options Order code Remote probe 3 m cable E2660 CO NO2 RP33 3 Remote probe 10 m cable E2660 CO NO2 RP33 10 Integrated 90 265 V...

Page 15: ...meter Flexible setting of analog output scales for each output Output zero and slope adjustment for calibration Free assignment of each of two relays to the chosen parameter Several relay control logi...

Page 16: ...register Error codes 01 Illegal function 02 Illegal data address 03 Illegal data value 04 Slave device failure details of last error 04 can be read from register 0x0008 Modbus holding registers Regist...

Page 17: ...ent for gas data 1 65535 512 0x00A7 167 40168 RW The change rate limit for gas data ppm gas unit s 1 32000 0 no limit 0 0x00A8 168 40169 RW Integrating filter time constant s 1 32000 seconds 0 no filt...

Page 18: ...8 RW Minimal on off time for relay RE1 0 1000 s 0 0x00DA 218 40219 RW Minimal on off time for relay RE2 0 1000 s 0 Addr Reg MHR RW Description Supported values dec Default 0x00DB 219 40220 RW Control...

Page 19: ...nt turn signaling off on analog output1 bit 3 0 1 in case the sensor is absent turn on signaling with low current high current on analog output1 if bit 2 0 this bit will be ignored bit 4 0 1 in case o...

Page 20: ...DC 32000 32000 ADC units 0 0x016E 366 40367 Slope adjustment for 2nd gas data 1 65535 0x016F 367 40368 The change rate limit for 2nd gas data gas unit s 1 32000 0 no limit 0 0x0170 368 40369 2nd Integ...

Page 21: ...Manufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Man...

Reviews: