E2660-CO-NO2
Rev 06.04.2021
CE marking
According to 2014/30/EU and 2014/35/EU, EN 50491-4-1:2012
EN 61000-6-3:2020, EN 61326-1:2013(EMC, emissions)
EN 61000-6-1:2019, EN 61000-6-2:2019(EMC, Immunity)
EN 60079-29-1:2016, EN 60079-29-2:2015 and EN 60079-29-3:2014
Relay option
Output relays
2 × SPST relays (closing contact),
250 VAC / 30 VDC, 5 A max
Alarm set-points
RE1: set 25 ppm
release 20 ppm
RE2: set 3 ppm
release 2.4 ppm
Other options
Remote probe
Protection IP65, default cable length 3.0 m;
max height 80 mm, max diameter 65 mm
6