Evikon PluraSens E2408DF User Manual Download Page 8

E2408DF

Rev 27.05.2021

Make certain that the cable gland is properly tightened to ensure the conformity to IP65
protection class.

The screwless quick connect spring terminals on the E2407 are suitable for a wide range
of wires with cross-section 0,2...1,5 mm

2

. The recommended wire stripping length is 8...9

mm. Push the spring loaded terminal lever, insert the wire end into the terminal hole and
release the lever.

Use twisted pair cable, e.g. LiYY TP 2×2×0,5 mm2 or CAT 5, to connect the device to the
RS485 network. Use one pair for A and B wires and the second pair for common 0V and
power +U wires. to connect the transmitter to the Fieldbus network.polarity must be
respected when connecting to an external RS485 network.

Overall length of all connections via the RS485 interface should not exceed 1200 m.

Both analog outputs can be independently changed between 4-20 mA and 0-10 V type
using jumpers J1 (OUT1) and J2 (OUT2). By closing pins on a specific jumper the related
output is 0-10 V, with an open jumper the output is 4-20 mA. Power restart is required after
changing the position of the jumpers.

NOTE! The outputs are not galvanically isolated from the external power supply and share
a common 0V. Allowed load resistance limits are stated in the Specifications table. To
power the instrument from an external power source, connect terminals 0V and +U to the
source. If the integrated mains power supply module is used, connect terminals L and N to
the mains.

NOTE! If the instrument is powered from mains, connect to 0V and +U terminals only light
external loads, which consume less than 30 mA in total, as the integrated mains supply
module capacity is limited.

NOTE! Actuator short-circuits should be avoided, to protect the instrument relays use
external fuses or safety switches.

When the detector is fixed and the external devices connected, place the lid back and fix it
with the screws.

8

Summary of Contents for PluraSens E2408DF

Page 1: ...PluraSens Differential pressure transmitter regulator E2408DF User Manual...

Page 2: ...ety requirements 4 Operating conditions 4 Installation and connections 5 Delivery set 9 Order code for E2408DF options 9 Configuring 9 Return to default settings 10 Emergency mode 10 Modbus RTU Commun...

Page 3: ...hPa Analog outputs 2 4 20 mA or 0 10 V user settable Digital interface RS485 Modbus RTU protocol Load resistance RL Us 3 V 22 mA for 4 20 mA RL 100 kOhm for 0 10 V mode Operating conditions 20 70 C 9...

Page 4: ...ty and improved repeatability especially near zero E2408 features two independent analog outputs OUT1 and OUT2 user selectable to 4 20 mA or 0 10 V RS485 Modbus RTU digital communication interface all...

Page 5: ...e the hoses of appropriate diameter 4 or 6 mm and length Put one end of the hose on the fitting in the bottom part of the device and fix the other end in the selected measurement area The port marked...

Page 6: ...ction diagram and table Version without PSU Version with PSU Jumpers J1 OUT1 type open 4 20 mA closed 0 10 V J2 OUT2 type open 4 20 mA closed 0 10 V X6 Reset Modbus network parameters to default X4 te...

Page 7: ...7 05 2021 X5 terminals optional L 90 265 VAC Phase N 90 265 VAC Neutral RE1 NO Relay 1 normally open terminal RE1 COM Relay 1 common terminal RE2 NO Relay 2 normally open terminal RE2 COM Relay 2 comm...

Page 8: ...y changed between 4 20 mA and 0 10 V type using jumpers J1 OUT1 and J2 OUT2 By closing pins on a specific jumper the related output is 0 10 V with an open jumper the output is 4 20 mA Power restart is...

Page 9: ...ransmitter regulator E2408DF shares all functionalities of the PluraSens multifunctional transmitter platform The features and options include Digital output change rate limiting filter Digital integr...

Page 10: ...fault bit 0 0 1 sensor present absent Read only bit 1 0 1 analog outputs activated deactivated 1 bit 2 0 1 in case of sensor absence turn signalling off on OUT 1 1 bit 3 0 1 In case of sensor absence...

Page 11: ...imit 168 RW Integrating filter time constant for pressure data s 1 32000 s 0 no filter 201 RW Parameter assigned to OUT1 0 none 1 temperature 2 pressure 9 forced Modbus control value set in 203 202 RW...

Page 12: ...ta 32000 32000 pressure units 258 R Measured temperature Cx100 signed integer 4000 12500 40 00 125 00 C 259 R Measured pressure 32000 32000 pressure units 261 RW 0 value of analog OUT1 32000 32000 pre...

Page 13: ...9200 38400 57600 9600 Data bits 8 8 Parity none odd even none Stop bits 1 2 1 Protocol Modbus RTU Modbus functions 03 Read multiple registers 06 Write a single register Error codes 01 Illegal function...

Page 14: ...anufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Manuf...