E2408DF
Rev 27.05.2021
217 RW**
Min on/off time for RE1
0...1000 s, default 0
218 RW**
Min on/off time for RE2
0...1000 s, default 0
219 RW**
Control logic for relay RE1
0:_, 1:_
↓↑
¯, 2:¯
↑↓
_, 3:_
↑
¯
↓
_,
4:¯
↓
_
↑
¯
220 RW**
Control logic for relay RE2
0:_, 1:_
↓↑
¯, 2:¯
↑↓
_, 3:_
↑
¯
↓
_,
4:¯
↓
_
↑
¯
221 RW**
LOW setpoint for relay RE1
-32000...+32000
222 RW**
HIGH setpoint for relay RE1
-32000...+32000
223 RW**
LOW setpoint for relay RE2
-32000...+32000
224 RW**
HIGH setpoint for relay RE2
-32000...+32000
255 RW**
Sensor control/status
see Emergency mode paragraph
257 R
Raw pressure data
-32000...+32000 pressure units
258 R
Measured temperature, °Cx100
signed integer, -4000...+12500
(-40,00...+125,00 °C)
259 R
Measured pressure
-32000...+32000 pressure units
261 RW**
0% value of analog OUT1
-32000...+32000 pressure units
262 RW**
100% value of analog OUT1
-32000...+32000 pressure units
263 RW**
0% value of analog OUT2
-32000...+32000 pressure units
264 RW**
100% value of analog OUT2
-32000...+32000 pressure units
* - the new value is applied after restart.
** - the new value is applied immediately.
*** -writing 42330 restarts the device immediately, no response on Modbus
Broadcast ID=0 may be used to assign a new ID to device with unknown ID
For registers 203, 204, 213, 214 the value is dynamic and not kept in EEPROM
Pressure unit is 10 Pa
12