Product description
Differential pressure transmitter-regulator E2408DF is a member of the new PluraSens®
family of multifunctional measurement instruments. The transmitter is intended for
measurement of pressure of air and non-aggressive gases with superb accuracy and no
offset drift.
The differential pressure is measured by a thermal sensor element using flow-through
technology. Compared with membrane based sensors, the method provides an extended
dynamic range, better long-term stability and improved repeatability, especially near zero.
E2408 features two independent analog outputs OUT1 and OUT2 user-selectable to 4-20
mA or 0-10 V. RS485 Modbus RTU digital communication interface allows easy instrument
configuration and integration into various automation systems. Two relays RE1 and RE2
with closing contacts can be used to switch various actuators.
Safety requirements
Always adhere to the safety provisions applicable in the country of use.
Do not perform any maintenance operation with the power on. Do not let water or foreign
objects inside the device.
Operating conditions
The device should be used in explosion-safe (non ATEX -rated) indoor areas, without
aggressive gases in the atmosphere.