E2218
Rev 14.05.2021
NOTE: 3 and 4 are available
starting from the Software
version 0x214 (dec. 532)
0x0008
(4)0009
R
Last error code
1...255
0
0x0011
(4)0018 RW Restarts counter
write ‘42330’ to restart the
device
-
0x00A2
(4)0163 RW
Zero adjustment for
temperature data, °C × 100
-32000...+32000
(-320.00...+320.00 °C)
0
0x00A3
(4)0164 RW
Slope adjustment for
temperature data, % ×
1000
-32000...+32000
(-32.000...+32.000 %)
0
0x00A4
(4)0165 RW
Change rate limit for
temperature data, °C × 100
/ s
1...32000 (0.01...320.00 °C/s),
0 = no limit
0
0x00A5
(4)0166 RW
Zero adjustment for
humidity data, % RH × 100
-32000...+32000
(-320.00...+320.00 % RH)
0
0x00A6
(4)0167 RW
Slope adjustment for
humidity data, % × 1000
-32000...+32000
(-32.000...+32.000 %)
0
0x00A7
(4)0168 RW
Change rate limit for
humidity data, %RH × 100
/ s
1...32000 (0.01...320.00 %
RH/s), 0 = no limit
0
0x00A8
(4)0169 RW
Integrating filter time
constant for all channels, s
1...32000 (seconds), 0 = no
filter
0
Reg
(hex)
MHR (dec)
RW Description
Supported values (dec)
Default
0x00C9
(4)0202 RW
Parameter tied to analog
output 1
0 - none
1 - temperature
2 - humidity
3 - dewpoint
4 - absolute humidity
9 - forced Modbus control,
value set in MHR (4)0204
2
0x00CA
(4)0203 RW
Parameter tied to analog
output 2
0 - none
1 - temperature
2 - humidity
3 - dewpoint
4 - absolute humidity
1