E2218
Rev 14.05.2021
Emergency mode
The current outputs of the transmitter may be programmed via Modbus commands
(register 255) to signal if the connection with the sensor is lost. The signal may be set to
3.8 mA or 21.5 mA.
Return to default settings
To reset the device’s Slave ID, baud rate and stop bit number to factory settings, proceed as
follows:
1. De-energize the device
2. Connect the X6 jumper
3. Turn on the device
4. De-energize the device
5. Disconnect the X6 jumper
6. Turn on the device
11