background image

E2610-VOC

Rev 24.03.2021

Connections

1. Detach the base of the enclosure by gently pulling along four guiding pins.

2. Attach the base to the wall with two screws. (see drawings below).

3. Use rounded cutouts on the side of the base to let in the cables from the power supply
and of the external devices as shown below.

12

Summary of Contents for E2610-VOC

Page 1: ...Solvent Vapor Detector E2610 VOC User Manual...

Page 2: ...e 6 Toluene 7 Xylene 8 Specifications 9 Product description 10 Safety requirements 10 Operating conditions 10 Installation guidelines 11 Connections 12 Operation 14 Maintenance 14 Calibration 14 Deliv...

Page 3: ...ensity to air 2 0 Conversion 1 ppm 2 38 mg m3 Boiling point 56 11 C Low explosive limit LEL vol in air 2 5 Upper explosive limit UEL vol in air 12 8 Odor Characteristic pungent smell Hazards Highly fl...

Page 4: ...Conversion 1 ppm 3 19 mg m3 Boiling point 80 C Low explosive limit LEL vol in air 1 2 Upper explosive limit UEL vol in air 7 8 Odor Hyacinth like odor Hazards Highly flammable Irritant Carcinogen May...

Page 5: ...ow explosive limit LEL vol in air 3 3 3 Upper explosive limit UEL vol in air 19 Odor The characteristic smell of alcohol Hazards Highly flammable Gas air mixtures are explosive Inhalation of vapors le...

Page 6: ...onversion 1 ppm 3 60 mg m3 Boiling point 77 1 C Low explosive limit LEL vol in air 2 Upper explosive limit UEL vol in air 11 5 Odor Sweet pear smell Hazards Flammable Short term exposure to high level...

Page 7: ...Upper explosive limit UEL vol in air 6 75 7 1 Odor Characteristic chemical smell Hazards Highly flammable Gas air mixtures are explosive Inhalation possible effects irritation eyes nose lassitude wea...

Page 8: ...s ortho xylene meta xylene para xylene Molar weight 106 Conversion 1 ppm 4 34 mg m3 Boiling point 144 4 C 139 C 138 35 C Low explosive limit LEL vol in air 0 9 1 1 Upper explosive limit UEL vol in air...

Page 9: ...265 VAC Power consumption 2 VA Digital interface UART Relay outputs 2 SPDT max 5 A 30 VDC 250 VAC Alarm Buzzer 85 dB Enclosure ABS plastic with ventilation slots wall mount protection class IP20 Dimen...

Page 10: ...ch the electronic components directly as they are sensitive to static electricity Connection diagrams can be found in the connections section The device might not perform correctly or be damaged if th...

Page 11: ...entioned conditions above will affect the coverage area of the device however the coverage area for a detector is usually between 2 5 to 5 meters radius For early leakage detection install the sensor...

Page 12: ...the enclosure by gently pulling along four guiding pins 2 Attach the base to the wall with two screws see drawings below 3 Use rounded cutouts on the side of the base to let in the cables from the po...

Page 13: ...2610 series devices are suitable for a wide range of wires with cross section 0 2 1 5 mm2 We recommend to strip the wire end by 5 6 mm and tin it or to use the wire end sleeves To connect the wire loo...

Page 14: ...70 of the LOW alarm setpoint If the gas level exceeds the HIGH alarm setpoint the bottom red LED starts flashing and the buzzer starts beeping at a rate of 2 Hz and also the relay RE2 switches over De...

Page 15: ...s Detector E2610 VOC Mounting accessories 2 screws and 2 plastic dowel plugs Order code for E2610 VOC options E2610 options Order code Integrated 90 265 V mains power supply module E2610 VOC 230 Integ...

Page 16: ...Manufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Manu...

Reviews: