www.cuiheat.com
126344-01A
11
INSTALLATION
Continued
Combustible
Material
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6, page 10, are
not met, you must have a hood. When using
a hood there are still certain minimum mantel
clearances required. Follow minimum clear
-
ances shown in Figure 7 when using hood.
Figure 7 - Minimum Mantel Clearances
When Using Hood
NOTICE: Surface temperatures
of adjacent walls and mantels be
-
come hot during operation. Walls
and mantels above the firebox
may become hot to the touch.
If installed properly, these tem
-
peratures meet the requirement
of the national product standard.
Follow all minimum clearances
shown in this manual.
NOTICE: If your installation does
not meet the minimum clear-
ances shown, you must do one
of the following:
• raise the mantel to an accept
-
able height
FLOOR CLEARANCES
The fireplace's required clearances to com
-
bustibles must be maintained. Consult your
fireplace manufacturer's installation instruc
-
tions for minimum clearances. If permitted by
the fireplace installation instructions, combus
-
tible material may be installed up to the bottom
edge of the fireplace face (see figure 8).
INSTALLING DAMPER CLAMP
ACCESSORY FOR VENTED
OPERATION
Note: When used as a vented heater, ap-
pliance must be installed only in a solid-fuel
burning fireplace with a working flue and con
-
structed of noncombustible material.
For Massachusetts Residents Only:
Instal-
lation of this vented gas log set in the Com-
monwealth of Massachusetts requires the
damper be permanently removed or welded
in the fully open position.
If your heater is a manually-controlled model,
you may use this heater as a vented product.
There are three reasons for operating your
heater in the vented mode.
1. The fireplace does not meet the clearance
to combustibles requirements for vent-free
operation.
2. State or local codes do not permit vent-
free operation.
3. You prefer vented operation.
Minimum
Noncombustible
Material
8"
Min.
12" 15" 18" 20"
2½"
6"
8"
10"
12"
Distances to
Underside of
Mantel
Hood
(GA6050 or
GA6053)
Top of
Fireplace
Opening
Underside
of Mantel
Shelf
Mantel Shelf