background image

page 4 (SD738-EI00 04/2004) 

Sensitivity 2.35 

±

0.85%/ft. 

Operating Temperature Range 

32

o

F to 100

o

F (0

o

C to 38

o

C) 

Alarm Sound Level 

85dB at 10 feet 

Indicator Light 

Red LED flashes once every 45 seconds 

Low Battery Life 

Up to 30 days 

Radio Frequency 

432MHz  

Wireless Range

 35m 

(115ft) 

Sounder Alarm Pattern; UL, EU 

Evacuation Temporal Pattern 

Sounder Alarm Pattern; ULC 

Continuous Beeps 

Relative Humidity 

10% to 85% 

Dimensions 

6” (153 mm) by 1.57” (40 mm) 

Typical range in a residential environment. 

 

SMOKE DETECTOR WITH OPTIONAL WIRELESS 
TRANSMITTER INFORMATION 
 

Wireless Installation Location 

The location of the wireless smoke detector affects the overall performance of 
the wireless system. In order to ensure the best possible signal reception, the 
following criteria should be respected whenever possible: 

 

Select an installation site that is free of obstacles that reflect and absorb 
radio frequency (RF) signals, as well as interference that may distort 
signals. Avoid installation near or in the path of strong RF fields (i.e. neon 
lights, computers), and on or near metal objects, circuit breaker boxes, air 
conditioners, and heater ducts since they may cause interference and 
reduce the module’s sensitivity

 

 

Select a site that is not susceptible to drastic temperature changes

 

 

Respect the maximum allowable distance between the smoke detector 
and the wireless receiver

 

WARNING: Do not cut, bend, or alter the antenna. Ensure that the 
electrical wires do not cross over the antenna when connected. 

Smoke Detector Zone Assignment 

When assigning the smoke detector to a wireless receiver and you are 
prompted to open and close the module’s cover (press anti-tamper switch), 
press the smoke detector’s Test button to assign it to the receiver.

 

Check-In Supervision 

The MG-SMK1 transmits a check-in supervision signal to the receiver at 
regular intervals. This value is pre-determined and cannot be programmed. 

Alarm Transmission 

Upon detection of an alarm condition (smoke) the detector will transmit an 
alarm signal every 30 seconds to the wireless receiver until the condition 
stops. Once the alarm condition has stopped, the detector will wait 5 
seconds then transmit a restore signal to the wireless receiver. The restore 
signal is transmitted only once to the receiver after an alarm condition has 
stopped. 

Low Battery 

If the smoke detector experiences a low battery condition, it will wait 5 minutes 
and then transmit a low battery signal to the receiver. The smoke detector will 
continue to transmit a low battery signal every 12 hours until the battery is 
replaced. 

Replacing the Battery 

After replacing the battery, test the detector to ensure proper functioning (refer 
to Testing the Smoke Detector). 

Testing the Smoke Detector 

It is strongly recommended to test the smoke detector a minimum of once 
every month. When the Test button is pressed, the smoke detector sends an 
alarm signal to the wireless receiver. If the smoke detector zone is defined as 

Delayed 24hr Fire Zone

, the alarm signal is not sent to the central 

monitoring station. If the smoke detector zone is defined as an 

Instant 24hr 

Fire Zone

, the alarm signal is immediately sent to the central monitoring 

station. In this case, contact the central monitoring station before performing 
the test to avoid a false alarm. Refer to the security system manual for more 
information on testing the security system. 
To test the smoke detector: 
1. 

If the smoke detector zone is an 

Instant 24hr Fire Zone

, contact the 

Central Monitoring Station to advise them of the test. 

2. 

Press and hold the Test button for approximately 3 seconds until the 
buzzer activates. 

3. 

If the zone is a 

Delayed Fire Zone

, the alarm will stop automatically. If 

the zone is an 

Instant Fire Zone

, enter a valid code # (PIN) to stop the 

alarm. 

Product compatibility: 

 

Sub-assembly part# MG-SMK1 is compatible with Magellan models 
6030, 6060 in 432MHz frequency range. 

 

WARNING: This device is only approved to function with Magellan 6060 
or 6030.  
 
WARNING: This device is not intended as life -saving device and should 
not be connected with any life saving device or fire system. This device 
is only intended to be used in residences. 
 
WARNING: If the smoke detector does not emit an alarm, connect or 
replace the battery and then re-test the detector. If the smoke detector 
still does not respond, contact your distributor. 

 

 

 

WARNING: LIMITATIONS OF SMOKE 
DETECTORS/TRANSMITTERS 

This smoke detector is designed to 

activate and initiate

 emergency action, but 

will only do so when used in conjunction with an authorized fire alarm system. 
This detector must be installed in accordance with NFPA standard 72. 
 

Smoke detectors will not work without power.

 AC or DC powered smoke 

detectors will not work if, for any reason, the power supply is cut off.  An alarm 
signal sent by the wireless transmitter in this detector may be blocked or 
reflected by metal before reaching the alarm receiver. Even if the signal path 
has been recently checked, blockage may occur if a metal object is moved into 
the path. 
 

Smoke detectors will not sense fires when smoke does not reach the 
detectors.

 Smoldering fires typically do not generate a large amount of heat, 

which is needed to drive smoke up to the ceiling where the smoke detector is 
usually located. For this reason, there may be large delays in detecting a 
smoldering fire with either an ionization-type detector or a photoelectric-type 
detector. Either one of them may only generate an alarm after flaming has 
initiated, which will generate the heat needed to drive the smoke to the ceiling. 
 
Smoke from fires in chimneys, in walks, on roofs, or on the other side of a 
closed door may not reach the smoke detector and generate an alarm. A 
detector may not quickly detect or sense at all, a fire developing on another 
level of a building. Alarm warning devices, such as bells or horns, may not alert 
people or wake up sleepers if they are located on the other side of closed or 
partly open doors, or on another level. Persons may not hear a warning device 
over the noise levels of a radio, air conditioner or appliances or traffic. For this 
reason, 

detectors are strongly recommended to be located on every level 

and in every bedroom within a building

. Alarm warning devices, however 

loud, may not warn hearing-impaired people or waken deep sleepers. 
 

Smoke detectors shall be located in any room where an alarm control is 
located, or in any room where alarm control connections to an AC 
source or phone lines are made.

 If detectors are not so located, a fire within 

any of these rooms could prevent the QED control from reporting a fire. 
 

Sensing limitations of smoke detectors.

 Ionization detectors and 

photoelectronic detectors are required to pass fire tests of the flaming and 
smoldering types. This is to ensure that both can detect a wide range of fires. 
Ionization detectors offer a broad range of fire-sensing capability, but 

they are somewhat better at detecting fast flaming fires than 
slow-smoldering fires. Photoelectronic detectors sense smoldering fires 
better than flaming fires, which have little, if any, visible smoke. Because 
fires develop in different ways, and are often unpredictable in their growth, 
neither type of detector is necessarily the best, and a given detector may 

not always provide early warning of a specific type of fire.  
 
In general, detectors cannot be expected to provide warning for fires 
resulting from inadequate fire protection practices, violent explosions, 
escaping gases that ignite, improper storage of flammable liquids like 

Reviews: